    GDWG-IV SF6 Gas Leakage Detector hits:

    General Information


    GDWG-IV SF6 Gas Leak Detector is infrared red type leak detector (NDIR technology). It is color OLED display and real-time shows SF6 concentration. It rapidly detects SF6 breaker, GIS leakage point and yearly leakage rate qualitatively and quantitatively. It’s a good device suitable for power supply department, installation and overhaul unit, power test institute.


    Application

    • High Voltage Switch Equipment
    • Rotor vane of helicopter
    • Gas transmission system
    • To detect fire extinguisher
    • Ventilation efficiency research of Buildings
    • To detect danger


    Advantages

    • No radiation.
    • No need to replace high pressure high pure argon gas regularly.
    • No need to approach high pressure gas.
    • No need to replace sensors regularly, cost-effective.
    • Stable performance, low maintenance cost. No need to make linear calibration every year.
    • No affect by moisture and environment pollution.
    • High sensitivity, up to 0.1ppmv (0.01ppmv for option.)
    • When serious leakage or the SF6 gas concentration is up to 100%, it will not be polluted or damaged.


    Features

    • 3.5inch OLED display.
    • Built-in Lithium battery.
    • User-defined alarm with sound and light.
    • High sensitivity and good stability.
    • Fast measurement speed, time is up to 3s.
    • Temperature and pressure compensation.
    • Only response for SF6 gas, not for other gas.
    • Small size, easy to carry, suitable for on-site working.
    • With gasbag non-slip straps, more comfortable to carry.
    • Data storage up to 8000groups.
    • Super-light aluminum with full shielding shell.
    • External package uses engineering plastic, with waterproof, dust-proof.



    Specification

    Measuring principle

    Non-dispersive infrared sensor (NDIR)

    Resolution

    0.1ppmv

    Measuring range

    0-1000ppmv

    Accuracy

    ±2%FS (0-1000ppm). Even the measuring range is over 5000ppm, the instrument will not be damaged.

    Repeat-ability error

    ≤±1%

    Sensitivity

    0.1ppmv (can be customized to 0.01ppm, for option)

    Response time

    3s

    Recovery time

    5s

    Stability

    ≤±20ppm, more than 1000hours

    Zero shift

    ≤±1%(F.S/year)

    Linear error

    ≤±1%

    Storage temperature

    -20+60℃

    Operation temperature

    -20+50℃

    Environment humidity

    0-95%RH

    Operation humidity

    0-95%(non-condensing)

    Sampling mode

    Built-in electromagnetic diaphragm pump, automatic slot-in type, flow up to 1L/min.

    Working voltage

    220VAC±10%,50Hz Or Built-in Li-battery, continuous working 12hours after full charge.

    Peak current

    <700mA

    Average power

    <2W.

    Operation air pressure

    800~1150hPa.

    Dimension

    140*235*83mm

    Weight

    About 1.5kg


    CONTACT US
    Address: F/10, Block B7, JinYinTan Modern Enterprise City, Dongxihu District, Wuhan, China
    Email: info@hvhipot.com
    Skype: hvhipot@hotmail.com
    Tel: +86-27-85568138
    Fax: +86-27-65606183
    NAVIGATION
  • Company

    Company

  • Product

  • News

  • Services

  • Contact us

  • русский

  • All Rights Reserved Copyright@HV Hipot Electric Co.,Ltd.