What types of protection can the relay protection tester test? Can line protection, transformer protection, and generator protection all be tested? In substations, power plants, and power test sites, there are many types of relay protection devices, and the corresponding test items for different protection functions are also different. Therefore, when choosing a relay protection tester, one should not only consider the output current and voltage, but also pay close attention to which protection functions the instrument can cover and whether it meets the on-site testing requirements.
The relay protection tester is mainly used to test the functions, action values, action time, action logic, and protection setting values of relay protection devices. Depending on the different tested equipment and protection principles, the common test objects in practical applications include line protection, transformer protection, generator protection, busbar protection, automatic backup power supply, and low-frequency load shedding, etc. By simulating electrical quantities such as current, voltage, frequency, and phase in actual operation, the action of the protection device can be verified.
In line protection testing, the application of the relay protection tester is very extensive. Common items include overcurrent protection, instantaneous protection, distance protection, zero-sequence protection, grounding distance protection, and direction protection, etc. For distance protection, corresponding impedance values need to be set for different protection segments, and fault current and fault voltage need to be simulated to check the action of the protection device in the first, second, and third segments. For zero-sequence protection and grounding protection, parameters such as zero-sequence current, zero-sequence voltage, and action time need to be tested. The relay protection tester can output corresponding electrical quantities according to the set values, providing complete testing conditions for the line protection device.
Transformer protection testing is also an important application direction of the relay protection tester. Common protections for transformers include differential protection, overcurrent protection, zero-sequence protection, overload protection, and gas protection, etc. Differential protection testing requires setting corresponding impedance values for different protection segments and simulating fault current and fault voltage to check the action of the protection device in the first, second, and third segments. For zero-sequence protection and grounding protection, parameters such as zero-sequence current, zero-sequence voltage, and action time need to be tested. The relay protection tester can output corresponding electrical quantities according to the set values, verifying the start-up value, action value, action time, and braking characteristics of the protection device according to the requirements.
For generator protection, the relay protection tester can also cover various common protection functions. Generator protection usually involves longitudinal differential protection, stator grounding protection, rotor grounding protection, negative-sequence protection, overcurrent protection, overvoltage protection, low-voltage protection, and loss-of-magnetism protection. The electrical quantities simulated by different protections are not exactly the same. For example, negative-sequence protection needs to focus on verifying the negative-sequence current and its action characteristics, while loss-of-magnetism protection usually involves voltage, current, and impedance parameter changes. Therefore, when conducting generator protection tests, the corresponding test methods need to be selected based on the specific protection principle.
In addition to line, transformer, and generator protection, the relay protection tester can also be used for busbar protection testing. Busbar protection usually makes a comprehensive judgment on multiple circuit currents, and during testing, different operation modes and fault states need to be simulated according to the actual protection logic. For example, the current relationship between internal faults and external faults on the busbar is different, and the relay protection tester needs to output multiple synchronous currents to verify the braking, locking, and action logic of the protection device. For some complex busbar protection systems, the ability to output multi-channel synchronous currents is particularly important.
The automatic backup power supply device is also a common object in relay protection testing. The backup power supply protection test focuses on checking whether the device can complete judgment and action according to the set logic under conditions such as loss of working power and normal backup power. The relay protection tester can test the startup conditions, action time and locking logic of the automatic reclosing device by simulating voltage disappearance, voltage recovery and different time relationships.
In addition, protection functions such as low-frequency load shedding, low-voltage load shedding, over-frequency protection, low-frequency protection and direction elements can also be tested using the relay protection tester. These protections have different requirements for parameters such as frequency, voltage, phase and time. During the test, precise simulation based on the protection settings is necessary. For example, when testing low-frequency protection, the output frequency can be gradually changed, the action frequency and action time of the protection device can be recorded, and then compared with the set values to determine whether the protection function is normal.
It should be noted that not all functions of the relay protection tester are exactly the same. Basic relay protection testers usually can meet the test requirements for conventional overcurrent, overvoltage, low voltage and time characteristics, while for transformer differential protection, generator complex protection, distance protection and busbar protection, attention should be paid to the number of current and voltage output channels, synchronization, output power, phase adjustment accuracy and protection test software functions. Therefore, when purchasing a relay protection tester, it should be selected based on the actual type of protection device, rather than simply judging based on price or larger output current.
The LDJB relay protection tester produced by HV HIPOT Electric Co., Ltd. is mainly used for on-site testing and inspection of relay protection and automatic devices in the power system. It can simulate output of parameters such as current, voltage, frequency, phase and time for different test objects. During actual use, parameters can be set according to the test requirements of various protection devices such as line protection, transformer protection, generator protection, busbar protection and other automatic devices, providing test conditions for relay protection debugging, inspection and fault analysis.
For on-site test personnel, when using the relay protection tester for testing, they also need to pay attention to test wiring, test methods and the corresponding relationship between protection settings. Especially for complex protections such as differential protection, distance protection and busbar protection, not only the protection action needs to be verified, but also the startup value, action time, action range and logical relationship need to be fully checked. After the test, the test data should be saved in time and compared with the protection setting values and historical test results to detect changes in protection performance.
Overall, the application scope of the relay protection tester is not limited to a certain type of protection device. From line protection to transformer protection, to generator protection, busbar protection and other automatic devices, it can conduct simulation tests according to specific test requirements. For power installation, maintenance, testing and equipment manufacturing units, choosing a relay protection tester with appropriate function configuration can improve on-site testing efficiency and is also conducive to standardizing the debugging and inspection of relay protection devices. The LDJB relay protection tester produced by Wuhan Guodian Xigao Electric Co., Ltd. can configure corresponding test schemes according to different protection types and test scenarios, meeting the conventional relay protection test requirements of the power system.