GD6900 Capacitance & Tan Delta Tester
• 7-inch touch LCD screen display.
• Calendar chip and large storage inside. Save testing result according to time order, check history record and print the result.
• The instrument data can be exported through U disk.
• The integrated insulation resistance test module can test polarization index, absorption ratio and insulation resistance.
• Multiple testing mode, with modes of internal high voltage, external high voltage, internal standard, external standard, GST/UST, self-excitation. High voltage(more than 10kV) dielectric loss test can be made in the situation of external standard outside high voltage.
• Test full sealed CVT (Capacitive Voltage Transformer) C1 and C2 dielectric loss and capacitance at the same time. Also test CVT transformation ratio and voltage angle difference.
• No need to dismantle cable to measure dielectric loss and capacitance of CVT.
• The dielectric loss and capacitance value of C0 in the upper end of CVT can be measured by using the reverse shielding method.
• High speed sampling signal. Inverter and sampling circuit inside are digitized controlled. Output voltage is adjusted continuously.
• LCR automatic measurement. Inductance, capacitance, resistance can be measured and displayed.
• Multiple protection of input voltage fluctuation, output short circuit, over-voltage, over-current, temperature, secure and reliable. Meanwhile, it has the function of grounding testing, that voltage boost is not permitted for non-grounding equipment.
• Frequency can be changed into 45Hz, 50Hz, 55Hz, 47.5Hz/52.5Hz, 45Hz/55Hz, 60Hz, 65Hz, 57.5Hz/62.5Hz, 55Hz/65Hz.
|
Working condition |
-15℃~40℃ |
RH<80% |
||||
|
Anti-interference principle |
Frequency conversion |
|||||
|
Power supply |
AC 220V, 60Hz |
Generator can be used. |
||||
|
High voltage output |
0.5kV~10kV |
Every 0.1kV |
||||
|
Accuracy |
2% |
|||||
|
Max. current |
200mA |
|||||
|
Capacity |
2000VA |
|||||
|
Self-excitation power |
AC 0V~50V/15A |
Single frequency: 45.0Hz, 50.0Hz 55.0Hz, 60.0Hz, 65.0Hz Automatic dual frequency conversion 45.0Hz/55.0Hz, 47.5Hz/52.5Hz 55.0Hz/65.0Hz, 57.5Hz/62.5Hz |
||||
|
Resolution |
tgδ: 0.001% |
Cx: 0.001pF |
||||
|
Accuracy |
∆tgδ: ±(reading*1.0%+0.040%) |
|||||
|
∆C x: ±(reading*1.0%+1.00PF) |
||||||
|
Measurement range |
tgδ |
Without limit |
||||
|
Cx
|
15pF < Cx < 300nF |
|||||
|
10kV |
Cx < 60nF |
|||||
|
5kV |
Cx < 150nF |
|||||
|
1kV |
Cx < 300nF |
|||||
|
CVT test |
Cx < 300nF |
|||||
|
LCR measurement range |
L>20H(2kV) |
R>10KΩ(2kV) |
||||
|
LCR measurement accuracy |
2% |
Angle resolution |
0.01 |
|||
|
CVT ratio range |
10~10000 |
|||||
|
CVT ratio accuracy |
3% |
CVT ratio resolution |
0.01 |
|||
|
Insulation resistance |
DC: 2.0-10kV accuracy: ±(reading×2%+0.1kV) |
|||||
|
10MΩ-10GΩ: ±(reading*5%+0.5M) |
||||||
|
10GΩ-100GΩ: ±(reading*5%+0.2G) |
||||||
|
100GΩ-1TGΩ: ±(reading*10%+0.5G) |
||||||
|
Dimension |
Main unit: 580(L)×380(W)×380(H) |
|||||
|
Accessory box: 430(L)×320(W)×140(H) |
||||||
|
Memory capacity |
100 groups, USB flash disk storage is supported. |
|||||
|
Weight |
Main unit: 23.5Kg |
|||||
|
Accessory box: 5.25Kg |
||||||