RPT-4632 Smart Substation Relay Protection Test System

RPT-4632 Smart Substation Relay Protection Test System

Brief Description:

RPT-4632 relay protection tester adopts modular design, with high-precision current and voltage amplifier modules, higher output accuracy, better stability, small size, light weight, rich test functions, etc. It uses a 9-inch high-definition touch LCD screen and full touch screen operation without buttons, making the operation more convenient and efficient. The instrument integrates conventional relay protection test, digital relay protection test, digital-analog hybrid relay protection test, merged unit test, intelligent terminal test, message analysis measurement, SCD file parsing and comparison, MMS related services and cloud testing functions, which can fully meet the test requirements of all types of relay protection and automatic devices in power plants, conventional substations, smart substations and new generation substations.


Product Detail

Product Tags

Features

• The current and voltage output accuracy of 0.05, meets the requirements of merging unit testing.

• Multiple output channels and large amplitude: the current can output 6-phase 20A or 3-phase 40A, and the voltage can output 4-phase 300V.

• 9-inch LCD touch screen, full touch screen operation, convenient and fast operation.

• Linux operating system, it runs stably compared with Windows CE operating system.

• Powerful abnormal working condition alarm function, completing voltage source short circuit, current source open circuit, overheating and signal distortion detection through pure hardware.

• Digital-analog mixed output mode meets the protection device testing requirements of "analog quantity + GOOSE".

• Gigabit port configuration meets the requirements of gigabit message reception and transmission.

• Powerful SV and GOOSE message analysis capabilities, with the function of message analyzer.

• With SCD file comparison and SCD file graphics function.

• With CID model file online reading and verification function; One-click completion of the internal CID file and SCD file consistency verification of the device.

• Cross-platform application software. It has local touch screen operation or computer online operation mode.

• It has cloud testing function, using cloud server technology, test templates and test cases can be downloaded and used through cloud server.

• It has one-key automatic test function to meet the test requirements of factory commissioning of protection devices.

• It supports the reading and verification of device protection settings, pressure plates and other information, and completes regular on-site verification.

• It has optical power measurement function.

• It has data serial forwarding function.

• It has GPS/BeiDou optical B code conversion function, which can be used as B code source.

• It has WIFI, Bluetooth, 4G Internet of Things communication function.

• It has automatic upgrade function, which can be directly upgraded using USB flash drive.

• It automatically generates test reports in PDF and CSV formats, and copies and archives them through USB flash drive.•

Specifications

AC Current

Setting Each phase output current amplitude, frequency and phase are independently adjustable.
Output range 6×0-20A/phase, or 3×0-40A/phase
Accuracy Typical value: <±0.2mA (0A--0.2A)

<±0.05%±0.1mA (0.2A--10A)

<±0.1% (10A--20A)

<±0.2% (20A—Imax)

Guaranteed value: <0.08%rd+ 0.02%rg, at (0--20A)

<0.15%rd+ 0.05%rg, at (20—Imax)

Resolution 1mA
Max. output power Pmax 6×20A/phase ≥85VA/phase, 3×40A/phase ≥160VA/phase
Current rise and fall time <100µs
Total harmonic distortion (THD%) Typical value: ≤0.1%(2A--Imax), ≤0.2%(0.2A--2A)

Guaranteed value: ≤0.5%(0.5A--Imax)

Frequency 10Hz -- 1kHz
Amplitude-frequency characteristics Amplitude change ≤±0.05%--±0.5%(10Hz--1kHz)
Output time <5A/phase, continuous output
Abnormal working condition alarm Automatic detection and alarm for overheating, overload, distortion and open circuit.

AC Voltage

Setting Each phase output current amplitude, frequency and phase are independently adjustable.
Output range 4×300V/phase
Accuracy Typical value: <±1mV(0V-2V)

<±0.05%(2V-Vmax)

Guaranteed value: <0.08%rd+0.02%rg (0-Vmax)

Resolution 1 mV (0.2V--10V), 10 mV(10V-300V)
Max. output power Pmax 4×300V/phase ≥90VA/phase
Voltage rise and fall time <100µs
Total harmonic distortion (THD%) Typical value: ≤0.1% (2V-Vmax)

Guaranteed value: ≤0.2% (2V--Vmax)

Frequency 10Hz--1kHz
Amplitude-frequency characteristics Amplitude change ≤±0.05%--±0.5%(10Hz--1kHz)
Output time Output time Continuous output under rated conditions
Abnormal working condition alarm Automatic detection and alarm for overheating, overload, distortion and open circuit.
Current and voltage synchronization error ≤10µs

Frequency

Sine signal 10Hz--1000Hz
Accuracy <1mHz (45Hz--65Hz)

<5mHz (10Hz--45Hz, 65 Hz--450Hz)

<10mHz (450 Hz--1000Hz)

Resolution 0.001Hz
Output characteristics Can superimpose 2-21 harmonics of any amplitude (less than rated value)
Sine signal 10Hz-1000Hz

Phase

Phase angle range 0-359.9°
Accuracy Typical value: ≤±0.1°

Guaranteed value: ≤±0.2°

Resolution 0.01°

DC Current

Output range 6×0-10A/phase, 3×0-20A/phase
Accuracy Typical value: <±1mA(0A-0.2A), ±0.5%(0.2A-Imax)

Guaranteed value: ±5mA, at (0A-0.2A),

0.3%rd+0.2%rg, at (0.2A-Imax)

Resolution 1mA

DC Voltage

Output range 4×400V/phase
Accuracy Typical value: <±4mV(0V-2V), ±0.2% (2V-Vmax)

Guaranteed value: ±5mV(0V-2V), <0.3%rd+0.2%rg, at(2V-Vmax)

Resolution 1mV (0.2V-10V), 10mV(10V-400V)

Small signal analog output

Channel 8 channels
Output range 0-7.07Vrms (RMS)
Accuracy Typical value:

<±0.1mV(0V-0.1Vrms); ±0.05%(0.1Vrms-7.07Vrms)

Guaranteed value: < 0.03 % rd + 0.02 % rg,at 0V-7.07 Vrms

Max. output current 1mA
Harmonic distortion <0.05%

Auxiliary DC Power Supply Output (Optional)

Channel 1group
Output range DC 110V / 220V switching
Max. output power Pmax 85W(110V), 170W(220V)

Fiber optic Ethernet interface

Quantity 8 pairs, 1 pair for Gigabit network
Interface type LC interface
Wavelength 100M port: 1310nm, Gigabit port: 850nm
Communication protocol IEC61850-9-2, GOOSE, IEC1588

Fiber optic serial interface

Quantity 4, 2 transmit and 2 receive
Interface type ST interface
Wavelength 820nm
Communication protocol IEC60044-8, IRIG-B, PPS
Electrical Ethernet interface quantity 2pcs
Interface type RJ45
Communication protocol MMS, TCP/IP
WIFI interface quantity 1
Bluetooth interface quantity 1
USB interface quantity 1
4G interface 1 (optional)

Binary In and Ouput

Binary In 8pairs
Input characteristics 8 pairs of input contacts are adaptive to empty nodes or with potential;

1-4 with potential contact flip level 20~250V (DC)

5-8 with potential contact flip level 9~28V (DC)

 

Electrical isolation 8 pairs of input electrical isolation
Impedance coefficient of empty contact threshold 3kΩ-5kΩ
Binary Output 4pairs
Type Common contact (response time <2ms)

Fast contact (response time <100μs)

DC capacity Vmax: 300V (DC)/Imax: 0.3A (excluding fast output)

Synchronous interface

GPS/BeiDou interface Built-in GPS/Beidou chip, supports GPS or Beidou timing
Optical B code transmission ST interface, 2pcs, multiplexed with FT3 port
Optical B code reception ST interface, 1pcs, multiplexed with FT3 port
PPS pulse reception ST interface, 1pcs, multiplexed with FT3 port
I588 timing interface LC, 1 pair, multiplexed with optical network port

Others

Rated Voltage 220V AC
Allowable Voltage 176V-253V AC
Rated frequency 50Hz
Allowable frequency 40-60Hz
Current 6A(max)
Screen 9inch Capacitive LCD screen (touch screen)
Size 315mm×240mm×140mm(W×H×D)
Weight < 8kg

 