China High Quality alat ukur megger Suppliers – GDHX-9500 Phase Detector – HV Hipot

China High Quality alat ukur megger Suppliers – GDHX-9500 Phase Detector – HV Hipot

Brief Description:


Product Detail

Product Tags

Related Video

Feedback (2)

As a way to provide you advantage and enlarge our organization, we even have inspectors in QC Crew and guarantee you our greatest assistance and product or service for Hipot Test Kit, Online Partial Discharge, Uhf Detecting Pd, We focus on to make excellent quality products to supply service for our clients to establish long-term win-win relationship.
China High Quality alat ukur megger Suppliers – GDHX-9500 Phase Detector – HV Hipot Detail:

General Information

GDHX-9500 Phase Detector is mainly used in electric power lines, phase and phase sequence calibration in substation, with main functions including electrical inspection, phase calibration and phase sequence measurement. It uses double shielding and brand new digital circuits, with strong anti-interference, accorded with EMC standards, suitable for various electromagnetic interference situations.

The high voltage phase signal of measured lead will be transmitted directly after treatment, the handset will receive and make phase comparison, determine the results after phase detection, real-time display phase angle difference and vector.It uses wireless transmission technology, safe and reliable, fast and accurate, suitable for using at different voltage levels (6V-500KV). When checking the grid structure, it is able to accurately identify the relative phase of different leads for the three-phase connected line, without any electrical connection between two measurement components, which makes the application of the measurement device very flexible and safe.

Security Matters

● Using wireless transmission technology, its basic working principle is real-time phase comparison.

● Please observe and follow the regulation to use this product, in order to ensure the safe operation of the instrument, the ends of X and Y detector are not allowed to make withstand voltage test.

● The metal head parts of the insulating rod is strictly prohibited to contact with any objects during the test.

● Please comply with the national power industry safety regulations of preventive test for safety tools and products.

● Please pay attention to the training and examination for staffs who work on high-voltage live lines or near the high-voltage lines.

● Phase calibration on live equipment must be carried out by insulating rod.

Note: The safe usage length and test standards of insulating rod for “Wireless Phase Detector”.

(Excerpting from “Electrical safety working regulations of State Grid Corporation”.)

1. Safety distance between staff and the charged body during live operation.

Voltage Level

10kV

35kV

66kV

110kV

220kV

330kV

500kV

Safety Distance

0.4M

0.6M

0.7M

1.0M

1.8M

2.2M

3.4M

2. The minimum effective insulation length of insulating rod during live operation.

Voltage Level

10kV

35kV

66kV

110kV

220kV

330kV

500kV

Min. effective insulation length

0.7M

0.9M

1.0M

1.3M

2.1M

3.1M

4.0M

Note: The test standard of insulating tools checking test (subsection): applying power frequency 75kV each 300mm for 1min, if no breakdown, no flashover and over-heat, it is considered as qualify.

Features

● Test voltage: 10V-500kV, suitable for different voltage level.

● Accuracy: self-calibrating error ≤±3°.

● Sampling speed: 10 times/s.

● Date and time setting: date and time adjustment, easy for users to browse, view the historical data.

● Back-light time setting: normally on, normally off, 0-999s can be set by user.

● Auto power off setting: 0-999mins can be set by user.

● In-phase: ≤20° is considered as in-phase (phase threshold within 0-90°, can be set by user. The system default is 20°.)

● Out-phase qualitative: >20° (phase threshold within 0-90°, can be set by user. The system default is 20°.)

● Field calibration function: on-site calibration for measured lead, ensure the accuracy of phase angle.

● Transmission distance between handset and X, Y detector: X≤150m, Y≤150m.

● Multiple mode design, with strong applicability, safer and more convenient.

● Unique human-computer interaction interface, simple operation.

● FCC antenna design, the signal is stronger and easier to penetrate the blocking of wall, door, or barrier.

● Double shielding, strong an-ti interference, in full accordance with EMC standards.

● Charts and data display, more convenient and easier to read.

● Qualitative measurement, display by sound and light signal.

● Quantitative measurement, real-time display phase angle difference, error≤5°.

● Phase sequence calibration, positive phase sequence, negative phase sequence (120°, 240°).

Specifications

Test voltage

10V-500kV

Power supply

Handset: No.5 AA alkaline battery 2 sections (1.5V)

X and Y detector: No.7 AA alkaline battery 2 sections (1.5V)

Wireless transmission distance

Visual distance 150m

In-phase

Phase angle deviation≤20° (threshold within 0-90°, can be set by user self. )

Out-phase

Phase angle deviation>20° (threshold within 0-90°, can be set by user self. )

Display accuracy

Quantitative measurement≤3°

Phase angle resolution

1°

Phase sequence measurement

Through 120° clockwise/240°anti-clockwise to determine and indicate phase sequence

Display

Positive display LCD, clearly display under the sunshine

Operation temperature

-35℃-+50℃

Storage temperature

-40℃-+55℃

Relative humidity

≤95% RH, Non-condensate

Handset

0.31kg

X detector

0.13kg

Y detector

0.13kg


Product detail pictures:

China High Quality alat ukur megger Suppliers –  GDHX-9500 Phase Detector – HV Hipot detail pictures

China High Quality alat ukur megger Suppliers –  GDHX-9500 Phase Detector – HV Hipot detail pictures


Related Product Guide:

Bear "Customer initially, High quality first" in mind, we do the job closely with our customers and supply them with efficient and skilled providers for China High Quality alat ukur megger Suppliers – GDHX-9500 Phase Detector – HV Hipot , The product will supply to all over the world, such as: Sri Lanka, Karachi, Congo, Our company offers the full range from pre-sales to after-sales service, from product development to audit the use of maintenance, based on strong technical strength, superior product performance, reasonable prices and perfect service, we'll continue to develop, to deliver the high-quality items and services, and promote lasting cooperation with our customers, common development and create a better future.
  • We are long-term partners, there is no disappointment every time, we hope to maintain this friendship later!
    5 Stars By Jean from Belize - 2017.02.28 14:19
    The company's products very well, we have purchased and cooperated many times, fair price and assured quality, in short, this is a trustworthy company!
    5 Stars By Hedda from Uruguay - 2018.12.11 11:26

    Send your message to us:

    Write your message here and send it to us

    Send your message to us:

    Write your message here and send it to us