China High Quality Capacitor System Factories – AC Resonant Test System for Generators GDTL – HV Hipot
China High Quality Capacitor System Factories – AC Resonant Test System for Generators GDTL – HV Hipot Detail:
GDTL series AC Resonant Test System for Generators can be used by adjusting inductance of the reactor, or adjusting the work way of resonant frequency of the system to achieve resonance. Both two methods can be used to achieve resonance. In the voltage boosting process, if the resonant point deviate, it can be found exactly by the way of fine tuning frequency, which ensure a high Q value and reduce power capacity and volume weight of test equipment.
Features
● Smaller size,lighter weight compared with same voltage level,same capacity generator AC withstand voltage test equipment.Single equipment is no more than 60kg, easy to move.
● Advanced principle of whole set device and new frequency & inductance modulation technology, strictly ensure generator power frequency withstand voltage test requirements. Wide application scope.
● Equipped with 20Hz-300Hz variable control source. Good protection and output waveform, high stability. With multiple working mode,easy to operate.
● Power supply of 220V or 380V, convenient for on-site power sourcing。
● Max.Q point can be found exactly by the mode of first inductance modulation and later frequency modulation, to avoid resonance deviation because of voltage boosting;
● Flexible configuration and strong extension. Meet all capacitive test object testing requirements in power system.
● Power frequency test mode or Variable frequency test mode.
● Multi-use, cost-effective.
Specifications
● Rated output voltage: 0 ~ 50kV (RMS) or below.
● Output frequency: 45 – 300Hz.
● Waveform: pure sine wave, THD ≤ 1%.
● Max. capacity: 2000kVA or below.
● Duty cycle: continuous working 15mins one time at full power output.
● Quality factor: 10 – 40.
● Frequency adjustment sensitivity: 0.1HZ, instability of <0.05%.
● Power supply: 220V or 380V ± 15%, 50HZ ± 5%.
|
GDTF- 100/50 |
|
|
Input voltage (V) |
380 |
|
Output voltage (kV) |
0- 50 |
|
Capacity (kVA) |
100 |
|
Application scope |
Generator–capacitance to the ground 0.07-0.13 μF |
|
10 kV (300 mm² ) cable ≤ 1 km |
|
|
Main configurations |
50kV/1A Fixed reactor 1 set |
|
50kV/1A Adjustable reactor 1 set |
|
|
Capacitive divider 50kV |
|
|
GDTF-150/50 |
|
|
Input voltage (V) |
380 |
|
Output voltage (kV) |
0- 50 |
|
Capacity (kVA) |
150 |
|
Application scope |
Generator–capacitance to the ground 0.13-0.2 μF |
|
10 kV (300 mm² ) cable ≤ 1.5 km |
|
|
Main configurations |
50kV/1.5A Fixed reactor 1 set |
|
50kV/1.5A Adjustable reactor 1 set |
|
|
Capacitive divider 50 kV |
|
|
GDTF- 225/50 |
|
|
Input voltage (V) |
380 |
|
Output voltage (kV) |
0- 50 |
|
Capacity (kVA) |
225 |
|
Application scope |
Generator–capacitance to the ground 0.2-0.27 μF |
|
10 kV (300 mm ² ) cable ≤ 2.5 km |
|
|
Main configurations |
50kV/1.5A Fixed reactor 2 sets |
|
50kV/1.5A Adjustable reactor 1 set |
|
|
Capacitive divider 50 kV |
|
|
GDTF- 360/60 |
|
|
Input voltage (V) |
380 |
|
Output voltage (kV) |
0- 60 |
|
Capacity (kVA) |
360 |
|
Application scope |
Generator–capacitance to the ground 0.27-0.33 μF |
|
Main configurations |
60kV/2A Fixed reactor 1 set |
|
60kV/2A Adjustable reactor 1 set |
|
|
Capacitive divider 60kV |
|
Product detail pictures:
Related Product Guide:
Our well-equipped facilities and excellent excellent management throughout all stages of creation enables us to guarantee total buyer satisfaction for China High Quality Capacitor System Factories – AC Resonant Test System for Generators GDTL – HV Hipot , The product will supply to all over the world, such as: Naples, Seychelles, Spain, With a wide range, good quality, reasonable prices and stylish designs, our products are extensively used in public placesand other industries. Our products are widely recognized and trusted by users and can meet continuously developing economic and social needs. We welcome new and old customers from all walks of life to contact us for future business relationships and achieving mutual success!