China High Quality Ct/Pt Metering Set Manufacturer – GDHG-106B CT/PT Analyzer – HV Hipot
China High Quality Ct/Pt Metering Set Manufacturer – GDHG-106B CT/PT Analyzer – HV Hipot Detail:
Features
● Finish all testing items by itself, no need to connect auxiliary equipment.
● Intelligent controller is adopted.
● Built-in printer, to print results easily.
● Large screen LCD, graphically display.
● Auto display excitation knee point value, 5% and 10% error curve.
● Save 3000 groups data and it is not lost after power down.
● With USB port. The data can be saved in USB disk and read by PC (WORD format file).
● Portable design, suitable for on-site test.
● Engineering plastic box with damping, strong and reliable.
Specifications
Main functions
CT (protection type, metering type) | PT |
Voltage current characteristic curve (excitation characteristic) | Voltage current characteristic curve (excitation characteristic) |
Auto calculate knee point value | Auto calculate knee point value |
Auto display 5% and 10% error curve | Turns ratio measurement |
Turns ratio measurement | Polarity determination |
Ratio error measurement | Ratio error measurement |
Phase measurement (angular difference) | Phase measurement (angular difference) |
Polarity determination | AC withstand test |
Primary current injection test | Secondary winding resistance measurement |
AC withstand test | Secondary burden measurement |
Secondary winding resistance measurement | |
Secondary burden measurement | |
Fast Test (Iron core demagnetization comprehensive test, complete excitation, ratio and polarity test at one time) |
Main parameters
Item | Parameter | |
Power supply | AC220V±10%, 50Hz | |
Output | 0-2500Vrms, 5Arms (20A peak) | |
Output current | 0-1000A | |
Accuracy of excitation | ≤0.5%(0.2% of the reading+0.3% of the range) | |
Secondary winding resistance measurement | Range | 0.1-300Ω |
Accuracy | ≤1.0% (0.4% of the reading+0.6% of the range) | |
Secondary actual burden measurement | Range | 5-500VA |
Accuracy | ≤0.5% (0.2% of the reading+0.3% of the range) ±0.1VA | |
Angular error measurement | Accuracy | 4min |
Resolution | 0.1min | |
CT ratio measurement | Range | ≤25000A/5A (5000A/1A) |
Accuracy | ≤0.5% (0.2% of the reading+0.3% of the range) | |
PT ratio measurement | Range | ≤500KV |
Accuracy | ≤0.5% (0.2% of the reading+0.3% of the range) | |
Operation environment | Temperature: -10℃-40℃, Humidity: ≤90%, Altitude: ≤1000m | |
Dimension & Weight | Dimension: 345mm × 445mm × 380mm Weight: about 30kg |
Product detail pictures:
Related Product Guide:
abide by the contract", conforms towards the market requirement, joins during the market competition by its good quality likewise as provides additional comprehensive and great services for customers to let them turn out to be big winner. The pursue of your enterprise, is the clients' fulfillment for China High Quality Ct/Pt Metering Set Manufacturer – GDHG-106B CT/PT Analyzer – HV Hipot , The product will supply to all over the world, such as: Turkey, moldova, Brazil, To let customers be more confident in us and get the most comfortable service, we run our company with honesty, sincerity and best quality . We firmly believe that it is our pleasure to help customers to run their business more successfully, and that our professional advice and service can lead to more suitable choice for the customers.
By Lisa from Hamburg - 2017.11.12 12:31
Although we are a small company, we are also respected. Reliable quality, sincere service and good credit, we are honored to be able to work with you!
By Kitty from Barcelona - 2017.06.16 18:23
Send your message to us:
Write your message here and send it to us