China High Quality Current Impulse Generator Factories – Impulse Voltage Test System – HV Hipot
China High Quality Current Impulse Generator Factories – Impulse Voltage Test System – HV Hipot Detail:
Features
● Complete equipment and wide voltage levels in the whole set of device.
● Small electric inductance in the return circuit of the impulse voltage generator, A band-stop filtering is adopted so that a standard impulse wave is still generated even under a large capacity load, and large load capacity.
● Large in voltage utilization coefficient.
● Convenient in wave adjustment, simple in operation, excellent in synchronization performance and reliable in motion.
● An automatic control technique is adopted in the constant-current charge, which is high automation and strong anti-interference capacity.
● A digital measurement and analysis system for the impulse test date are adopted, which increase the technical level and the efficiency of the impulse voltage tests.
Specifications
Impulse voltage grade | 100kV-7200kV |
Standard lightning wave | 1.2±30%/50±20%µS |
Peak oscillation | <5% |
Standard switching wave | 250±20%/2500±60%µS |
Virtual front time of oscillating lightning wave | ≤15µS |
Virtual front time of oscillating switching wave and virtual front time of oscillating switching impulse wave |
15µS-1mS |
The minimum output voltage | ≥10%Un |
Charging voltage instability | <±1% |
Synchronizing range | ≥20% |
Synchronous discharge error rate | <2% |
Ignition range | 10%~100% |
Working time | ≥70%UN Discontinuous work (charge-discharge 300s/time) <70%nn Continuous work (charge-discharge 120s/time) |
Generator efficiency: lightning wave (no load) | ≥90% |
Time to chopping | 2~5µS |
Product detail pictures:
Related Product Guide:
Our products are broadly regarded and reliable by end users and can meet up with constantly transforming financial and social requires of China High Quality Current Impulse Generator Factories – Impulse Voltage Test System – HV Hipot , The product will supply to all over the world, such as: Cyprus, Adelaide, Irish, Our company will continue to serve customers with best quality, competitive price and timely delivery & the best payment term! We sincerely welcome friends from all over the world to visit& cooperate with us and enlarge our business. If you are interested in our products, please do not hesitate to contact us, we will be happy to provide you with further information!