General Information
GDSF-411CPD SF6 gas comprehensive analyzer is a portable device designed to measure SF6 gas dew point, purity and decomposition product. The core component with chilled mirror method is used to test dew point, European sensor with infrared method to test SF6 gas purity and electrochemical sensor from Membrapor to test SF6 gas decomposition product. Besides, we also adopt professional hardware chips and excellent software algorithms of STMicroelectronics.
Application
Features
Specification
SF6 Humidity
Measurement method | Chilled mirror method (Stirling Refrigeration) |
Measurement range | Dew point -100℃–+20℃(90s for single point measurement), error: better than ±0.2℃ |
Repeat-ability | ± 0.1 ℃ |
Resolution | 0.01℃ |
Display unit | ℃, ppm, ℃ P20(converted value at 20℃) |
SF6 Purity
Measurement method | Infrared Measurement Principle (NDIR series sensors) |
Measuring range | 0 ~ 100% SF6, error: better than ± 0.3%F.S. |
Response time | [90%] 60s |
Repeatability | ± 0.3% |
Resolution | 0.01% |
Display unit | % |
SF6 Decomposition Products
Measurement method |
Electrochemical Measurements Principle (Electrochemical series sensors from Membrapor) |
Measurement range |
SO2: 0 ~ 200ppmv H2S: 0 ~ 200ppmv CO: 0 ~ 500ppmv HF: 0 ~ 50ppmv |
Accuracy |
SO2: 10ppmv ±3% H2S: 10ppmv ±3% CO: 50ppmv ±4% HF: 10ppmv ±3% |
Repeat-ability |
SO2: 10ppmv ±2% H2S: 10ppmv ±2% CO: 50ppmv ±2% HF: 10ppmv ±2% |
Resolution | 0.01ppmv |
Display unit | ppmv |
General Parameters
Power supply | 220VAC±10%, 50Hz, AC/DC use, continuous working is more than 8 hours. |
Use environment temperature | -20–+60℃ |
Environment humidity | 90%RH |
Measurement value influence | No effect of pressure and flow |
Dimension | 570*420*280mm |
Weight | Not more than 20kg. |
Accessories
Main Tester |
1 piece |
Adapter |
1 set |
Teflon pipe (include flow adjustment valve and fast connector) |
1 set |
Tail pipe |
1 set |
Spare parts |
1 set |
Charger |
1 piece |
User’s Guide |
1 piece |
Test Report |
1 piece |
Product detail pictures:
Related Product Guide:
Sticking for the belief of "Creating items of top of the range and creating buddies with people today from all over the world", we normally put the interest of shoppers in the first place for China High Quality Hf Measurement Factory – GDSF-411CPD SF6 Gas Comprehensive Analyzer – HV Hipot , The product will supply to all over the world, such as: Portugal, Sudan, Porto, With the goal of "zero defect". To care for the environment, and social returns, care employee social responsibility as own duty. We welcome friends from all over the world to visit and guide us so that we can achieve the win-win goal together.