China High Quality partial discharge test equipment Factories – GDJF-2008 Partial Discharge Analyzer – HV Hipot

China High Quality partial discharge test equipment Factories – GDJF-2008 Partial Discharge Analyzer – HV Hipot

Brief Description:


Product Detail

Product Tags

Related Video

Feedback (2)

We've been convinced that with joint efforts, the enterprise between us will bring us mutual benefits. We are able to assure you product or service quality and aggressive cost for Discharge Circuit, Series Capacitance Voltmeter Can Measure, Capacitance And Tan Delta Test Set China, "Making the Products and solutions of Superior Quality" may be the eternal target of our company. We make unremitting attempts to comprehend the objective of "We Will Often Preserve in Pace along with the Time".
China High Quality partial discharge test equipment Factories – GDJF-2008 Partial Discharge Analyzer – HV Hipot Detail:

GDJF-2008 Partial Discharge Detector is measuring partial discharge for the products such as transformers, mutual inductors, HV switches, zinc monoxide arresters and power cables. It also can make type tests and monitor insulation operation.
This type has the advantages of high sensitivity, wide range of capacitance, being well equipped for input unit impedance detecting and more variants of frequency bands (9 in all). After proper setting, the discharge impulse amount can be read directly. The indicating and digital meters are shown simultaneously.
This detector is widely applied in power stations, manufacturers, and institutions.

Use Condition

● Ambient temperature: 0-40℃±2℃.
● Relative humidity: ≤80%
● Power supply: 220V±10%, 50HZ.
● No violent vibration and mechanical shock.
● The device should be placed in the environment with no dust and corrosive, good ventilation. It should not be interfered by strong electromagnetic.
● Earthing requirements: earthing resistance <1Ω.
● Capacitance range to be tested 6PF-250μF.
● Testing sensitivity (shown in Table.1).

Input unit No.

Tuning capacitance

Unit

Sensitivity(pC) (Unsymmetrical circuit)

1

6-25-100

pF

0.02

2

25-100-400

pF

0.04

3

100-400-1500

pF

0.06

4

400-1500-6000

pF

0.1

5

1500-6000-25000

pF

0.2

6

0.006-0.025-0.1

mF

0.3

7

0.025-0.1-0.4

mF

0.5

8

0.1-0.4-1.5

mF

1

9

0.4-1.5-6.0

mF

1.5

10

1.5-6.0-25

mF

2.5

11

6.0-25-60

mF

5

12

25-60-250

mF

10

7R

Resistance

 

0.5

● Amplifier band
Low terminal: 10KHZ, 20 KHZ, 40 KHZ (optional)
High terminal: 80 KHZ, 200 KHZ, 300 KHZ (optional)

● Amplifier gain adjustment
Coarse control – there are 6 gears for coarse tuning, the gain of each gear is 20±1db
Fine control ≥ 20 db

● Time windows
Width of window, adjustable 15o—150o
Window position, adjustable 0o—170o
Two windows can be opened simultaneously or separately.

● Discharge meter
Digital display
PD display: LED 3½ digits
0-100.0 limit of error <±3% (full scale)

● Ellipse time base
Frequency: 50Hz and arbitrary frequency
Elliptic display color is yellow
Elliptic rotation: each gear is 30°, 180 ° rotation can be made.
Display: ellipse – straight line
High frequency time base elliptical input voltage less than 220 V, intake power < 1 VA

● Waveform lock
Lock required waveform of any time to facilitate observation and analysis

● Testing Voltage meter
Range: 100KV (Can be expanded)
Display 31/2 digital voltage meter
Accuracy: better than ±2% (full scale)

● Inside, outside the zero-mark function
● Dimensions: 450×450×190 mm
● Weight: about 16kg


Product detail pictures:

China High Quality partial discharge test equipment Factories –  GDJF-2008 Partial Discharge Analyzer – HV Hipot detail pictures

China High Quality partial discharge test equipment Factories –  GDJF-2008 Partial Discharge Analyzer – HV Hipot detail pictures


Related Product Guide:

owing to very good support, a variety of high quality merchandise, aggressive costs and efficient delivery, we love an excellent name among the our clients. We are an energetic company with wide market for China High Quality partial discharge test equipment Factories – GDJF-2008 Partial Discharge Analyzer – HV Hipot , The product will supply to all over the world, such as: Saudi Arabia, Sierra Leone, Georgia, Welcome to visit our company, factory and our showroom where displays various products that will meet your expectation. Meanwhile, it is convenient to visit our website, and our sales staff will try their best to provide you the best service. Please contact us if you need more information. Our aim is to help customers realize their goals. We are making great efforts to achieve this win-win situation.
  • The company has rich resources, advanced machinery, experienced workers and excellent services, hope you keep improving and perfecting your products and service, wish you better!
    5 Stars By Astrid from Mozambique - 2018.12.11 11:26
    The accounts manager made a detailed introduction about the product, so that we have a comprehensive understanding of the product, and ultimately we decided to cooperate.
    5 Stars By Marcia from Hanover - 2018.10.09 19:07

    Send your message to us:

    Write your message here and send it to us

    Send your message to us:

    Write your message here and send it to us