China High Quality Sf6 Dew Point Tester Factory – GDWG-III SF6 Gas Leakage Detector – HV Hipot
China High Quality Sf6 Dew Point Tester Factory – GDWG-III SF6 Gas Leakage Detector – HV Hipot Detail:
Product Description
GDWG-III SF6 gas leakage detector, with non-dispersed infrared (NDIR) technology, is mainly used to pinpoint and measure SF6 leakage on GIS and refilling equipment within power industry.
The annual leakage rate of SF6 gas electrical equipment is measured with bandaging method. At the same time, the equipment is widely used in power supply bureau, substations, high voltage switch company, laboratory hood and scientific test.
Application
● High voltage switchgear
● Helicopter rotor blades
● Gas transmission system
● Fire extinguisher
● Ventilation rate study
● Hazardous material
● Tank
Advantages
● No radioactive risk.
● No need to replace high purity argon gas regularly.
● No need to replace sensor regularly, cost-effective.
● No need to make linear calibration every year, no wearing parts.
● Not effected by humidity, environment pollution or data drift.
● When there is severe leakage or SF6 gas concentration is up to 100%, it will not be polluted or damaged.
Features
● To measure SF6 gas leakage qualitatively and quantitatively.
● To locate SF6 gas leakage point.
● Parameters like SF6 gas concentration, temperature, humidity, power indicator, date and diaphragm pump status are displayed.
● User-friendly interface.
● Use NDIR technology and advanced sensor from Germany.
● Fast test speed and good repeatability, data is stabilized within 10s.
● With temperature and pressure compensation.
● No false alarm, no gas except SF6 responses.
● Non-contact gas measurement ensures that sensor won’t be poisoned at any concentration rate.
● Thermostatic chamber ensures no temperature drift at ambient temperature for sensor.
● 3.5inch OLED display, legible in the strong sunlight.
● Built-in lithium battery, standby time is long.
● Pipelines is customized as per request.
● Pump suction sampling ensure good sealing of gas path under test.
● More than 100 groups of test data are stored based on gas concentration and test time, easy to query.
● The outer casing is high strength, fully shielded, ultra-lightweight ABS material structure.
Specifications
● Measuring principle: Non-dispersive infrared sensor (NDIR)
● Measuring range: 0-1000ppm SF6
● Resolution: 0.1ppmv
● Accuracy: ±2%FS (0-1000ppm)
Even the measuring range is over 5000ppm, the instrument will not be damaged.
● Repeatability error: ≤±1%
● Sensitivity: 1ppmv
● Response time: ≤10s
● Recovery time: ≤15s
● Stability: ≤±20ppm, more than 1000hours
● Sampling mode: pump suction type, flow up to 1L/min.
● Zero shift: ≤±1%(F.S/year)
● Linear error: ≤±1%
● Peak current: <700mA
● Average power: <2W.
● Operation air pressure: 800-1150hPa.
● Environment humidity: 0-95%RH
● Storage temperature: -20~+60℃
● Operation temperature: -20~+50℃
● Operation humidity: 0-95%(non-condensing)
● Working voltage: 220VAC±10%,50Hz Or Built-in Li-battery, continuous working 6hours after full charge.
● Dimension: 220×250×120mm
● Weight: about 2kg
Accessories
| Main unit | 1 set |
| Charger | 1 piece |
| Hand-held probe | 1 piece |
| Anti-slip belt | 1 piece |
| Hose 600mm | 1 piece |
| User’s guide | 1 copy |
| Warranty card | 1 copy |
Product detail pictures:
Related Product Guide:
We're committed to providing easy,time-saving and money-saving one-stop purchasing service of consumer for China High Quality Sf6 Dew Point Tester Factory – GDWG-III SF6 Gas Leakage Detector – HV Hipot , The product will supply to all over the world, such as: Indonesia, Nairobi, Las Vegas, Since always, we adhering to the "open and fair, share to get, the pursuit of excellence, and creation of value"values, adhere to the"integrity and efficient, trade-oriented, best way , best valve" business philosophy. Together with our all over the world have branches and partners to develop new business areas, maximum common values. We sincerely welcome and together we share in global resources, opening up new career together with the chapter.
Cooperate with you every time is very successful, very happy. Hope that we can have more cooperation!





