GDF-3000A DC System Earth Fault Detector

GDF-3000A DC System Earth Fault Detector

Brief Description:

DC system insulation faults, DC mutual faults and AC power failures are faults that are prone to occur and are harmful to the power system, and endanger the normal operation of the power system.


Product Detail

Product Tags

General Information

DC system insulation faults, DC mutual faults and AC power failures are faults that are prone to occur and are harmful to the power system, and endanger the normal operation of the power system.

In order to better help field maintenance personnel to quickly and accurately find DC faults, our company has developed a DC fault finder by years of efforts and summing up a large number of field experiences.

The DC grounding finder uses a high-precision current clamp meter to detect and locate faults using the DC current difference in the fault loop. The fast FFT transform technology is introduced into the DC fault finding device, to detect various types of insulation faults, DC mutual faults, and AC power failures in DC systems with different voltage level (24V (optional), 48V, 110V, 220V).

With the increasing requirements for safe operation of power systems, the requirements for various types of DC fault finding in power systems will also become higher and higher. Therefore, high-precision, insulation trend analysis will become a basic requirements of the instrument for power systems' new generation DC grounding search.

Main functions

(1) System-to-ground voltage measurement function, the instrument can measure the system-to-ground voltage, negative-to-ground voltage, system voltage, and can realize the voltage monitoring range of 0-300V;
(2) System insulation impedance measurement function, the instrument can measure the insulation resistance of the system to ground, the negative insulation resistance to the ground, the balance bridge size detection, the measurement range is 0-999.9KΩ;
(3) AC power detection function, the instrument can judge the AC power failure in the DC system, and can measure the AC voltage value in the DC system, the AC voltage measurement range is 0-280V;
(4) System distributed capacitance measurement function, the instrument can measure the distributed capacitance of the system and display in real time;
(5) Ring network detection and positioning function, the instrument can detect various ring network faults in the two bus bars, including positive ring, negative ring, bipolar ring and bipolar ring, etc., and can be realized by waveform display and direction display to locate the fault point of the ring network;
(6) The device has amplitude modulation, reset, current waveform selection and working mode selection function, which can realize the search and location of high resistance ring network faults.
(7) Branch insulation resistance measurement and insulation fault location function, the instrument measures the insulation resistance of each branch to ground, and can realize the location of insulation fault points through waveform display and direction display;
(8) Fault current spectrum analysis function, the device effectively extracts the signal amplitude of the measured current frequency point, and improves the detection precision by spectrum analysis function of current change with fast FFT transform ;
(9) Ammeter function, the device can be used as a high-precision ammeter, and the current measurement resolution can reach 0.01mA;
(10) Waveform curve display and direction display function. When using the detector to detect the measured branch, it will display the current change of the measured branch in the form of a waveform curve on the screen, which is convenient for the user to realize the fault point quickly and accurately. Find the direction of the fault point when there is a ring fault and a ground fault.

Features

● High reliability design
The device adopts imported 32-bit microcontroller as the main system, and the hardware design strictly follows the power and electromagnetic compatibility related standards. The internal redundancy mode is adopted to ensure the reliability of the device and the device under test.

● Precision material selection
The device adopts high-precision collector as the signal acquisition unit, and the voltage sampling adopts high-precision imported analog-digital conversion chip, voltage and impedance are measured accurately;

● Humanized human-computer interaction interface
Both the analyzer and the detector use a TFT liquid crystal display for users to view information;
The operation is simple and fast, and when the detection of different branches is realized, only one start button can be completed;
The test results are straightforward and the test results can be presented to the user in a variety of display formats, including grounding or not waveform, insulation levels, insulation resistance, leakage current, and direction information.

● Intelligent detection and recognition system
The analyzer automatically recognizes the system voltage level;
The analyzer can determine the ring fault category;
After the detector and analyzer information are synchronized once, it will not affected by the detection distance;
When the detector is inspecting, the collector can clamp a single power cord or clamp multiple power cords to improve detection efficiency;
After the detector test is completed, if the tested branch has a ring network or insulation fault, the direction information of the fault point relative to the test point is determined.

● Complete testing function and ability to handle faults
The wireless data transmission module is built in between the analyzer and the detector for communication. The test function and display information are complete, and can deal with various ring networks and insulation faults in the DC system.
The analyzer has a variety of combined working mode by selecting functions of “Amplitude Modulation”, “Waveform” and “Mode”, which can adapt to various complex application environments.

● High security
The device adopts the micro-amplitude detection signal and the high-resolution DC detection collector to realize fault detection and positioning, and has no influence on the DC system.

Technical Specifications
Specifications of Analyzer
Working Voltage DC 22-300V.
Environment temperature -20℃—55℃
Relativity humidity 0—90%
DC voltage measurement
DC voltage measurement range 22-300V
DC voltage measurement resolution 0.1V
DC voltage measurement accuracy ±0.5% @ 220V DC power supply(180V-286V)
@110V DC power supply(90V-143V)
AC voltage measurement
Measurement AC and DC string voltage 10-280v
AC voltage measurement resolution 0.1V
AC voltage measurement accuracy 0.5%
Insulation resistance measurement
Insulation resistance measurement range 0-999.9KΩ
Insulation resistance measurement resolution 0.1KΩ 
Insulation resistance measurement accuracy ≤±5% Ri <10KΩ display specific value
10KΩ≤Ri≤500KΩ ±5%
Detect bridge amplitude adjustment range  0mA, 0.25mA, 0.5mA , 1mA, 2mA
Detect ring network resistance range less than 50KΩ
System distributed capacitance measurement
System distributed capacitance measurement range 0-999.9uF  accuracy C <10uF or C>200uF: display specific value; 10uF≤C≤200uF: ±10% or ±3uF;
Detection waveform type selection: sine wave, square wave;
System ground resistance measurement 0-1000kΩ
Detection waveform type selection sine wave, square wave
Working mode forced signal start, automatic signal start
Display media and resolution TFT, 320x240
Specifications of Detector
Insulation resistance measurement
Insulation resistance measurement range 0-500KΩ
Insulation resistance measurement resolution 0.1KΩ
Insulation resistance measurement accuracy Ri <10KΩ display specific value
10KΩ≤Ri≤500KΩ ±10%
Spectrum analysis range
Number of spectrum analysis channels 1
Spectrum analysis frequency range 0.125-12.5Hz
Frequency resolution 0.125Hz
Current waveform display period 8s;
Detectable feeder current range 0-2A;
Current measurement range -100-+100mA;
Current measurement resolution 0.01 mA
Display media and resolution TFT, 320x240
Wireless communication technical indicators
Rate 2Mbps, because the air transmission time is very short, the collision phenomenon in wireless transmission is greatly reduced.
Multi-frequency point  125 frequency points, meeting the needs of multi-point communication and frequency hopping communication
Ultra-small built-in 2.4GHz antenna, small size, 15x29mm
Low power consumption When operating in the answer mode , fast air transmission and start up time greatly reduce current consumption
Accessories
Detector 1 pc
Analyzer 1 pc
Adapter 2 pcs
Current clamp 1 pc
Test Lead(with crocodile clamp) 1 pc
Carry case 1 pc
User’s Guide 1 pc
Factory Test Report 1 pc