GSH-NNA-30/250-400 Mobile Heavy-Duty SF₆ Gas Recovery Unit | Oil-Free SF₆ Recovery, Purification & Liquefaction Cart

GSH-NNA-30/250-400 Mobile Heavy-Duty SF₆ Gas Recovery Unit | Oil-Free SF₆ Recovery, Purification & Liquefaction Cart

Brief Description:

GSH-NNA-30/250-400 heavy-duty SF6 gas recovery unit: 30m³/h recovery rate, 250m³/h high-capacity vacuum, 400kg liquefied storage. Integrates recovery, vacuum, deep purification, liquefaction and refilling. PLC auto control, multi-stage safety protection. Mobile industrial design for large GIS & EHV switchgear.


Product Detail

Product Tags

Features
GSH-NNA-30/250-400 is a heavy-duty industrial-grade SF₆ gas handling system designed for large-scale power utilities, switchgear manufacturing plants, EPC contractors and third-party testing institutions. It is dedicated to high-efficiency SF₆ gas recovery, deep vacuumizing, multi-stage purification, compression liquefaction, large-capacity storage and pressure-regulated refilling during installation, major maintenance and decommissioning of 110kV ~ 500kV large-capacity GIS, EHV SF₆ circuit breakers, instrument transformers and gas-insulated busbars.
It adopts a two-stage oil-free SF₆ dedicated compressor with positive & negative pressure recovery mode, achieving a recovery rate of 30m³/h and final recovery pressure as low as ≤10kPa, minimizing residual gas emission. The 250m³/h high-capacity dual-stage rotary vane vacuum pump ensures deep vacuum degree ≤5Pa, fully meeting the strict vacuum requirements of high-voltage gas-insulated equipment. The multi-stage deep purification system includes high-efficiency particle filters, molecular sieve dryers and coalescing oil-mist separators, effectively removing moisture, decomposition products, oil residues and dust particles. Recovered gas meets IEC 60480 reuse standards and can be directly refilled into equipment.
Equipped with a 7-inch PLC touch screen, the unit supports one-key fully automatic operation and manual step-by-step control. It has built-in comprehensive safety protection mechanisms including over-pressure, over-current, over-temperature and low oil level alarms. The heavy-duty mobile cabinet structure with reinforced casters and traction handle is suitable for both on-site substation operation and fixed workshop use. It realizes closed-loop large-volume SF₆ gas management, reduces gas emission, lowers operation costs and meets environmental protection and production efficiency requirements.
Specifications
Parameter Specification
System Functions SF₆ recovery, deep vacuumizing, purification drying, liquefied storage, pressure-regulated refilling
Recovery Performance  
Recovery Rate 30 m³/h (at initial pressure 0.8MPa)
Final Recovery Pressure ≤ 10 kPa (absolute, negative pressure deep recovery)
Compressor Type Two-stage oil-free SF₆ special compressor
Vacuum Performance  
Vacuum Pumping Speed 250 m³/h
Ultimate Vacuum ≤ 5 Pa
Vacuum Rise Rate ≤ 400 Pa / 24h
Vacuum Pump Type Dual-stage rotary vane vacuum pump
Purification Performance  
Particulate Filtration ≤ 0.1μm, 99.99% efficiency
Moisture Content After Purification ≤ 40 ppmV
Oil Content After Purification ≤ 10 ppmW
SF₆ Purity After Recovery ≥ 98% by volume
Dryer Regeneration Vacuum heating activation regeneration supported
Storage Tank 400kg nominal liquefied storage capacity, pressure vessel certified
Design Pressure of Tank 5.0 MPa
Control Mode PLC + 7" touch screen, fully automatic / manual dual mode
Safety Protection Over-pressure, over-current, over-temperature, low oil level alarm, emergency stop, safety valve
System Leakage Rate ≤ 0.5% per year
Cooling Mode Air-cooled, no external water source required
Input Power Supply AC 380V ± 10%, 50Hz, three-phase
Operating Temperature -10℃ ~ +50℃
Ambient Humidity ≤ 85% RH (non-condensing)
Structure Form Heavy-duty mobile cabinet type with brake casters and traction handle

 