GDHX-9700 Phase Detector

GDHX-9700 Phase Detector

Brief Description:

GDHX-9700 Phase Detector is mainly used in electric power lines, phase, and phase sequence calibration in substation, with main functions including electrical inspection, phase calibration and phase sequence measurement.


Product Detail

Product Tags

General Information

GDHX-9700 Phase Detector is mainly used in electric power lines, phase, and phase sequence calibration in substation, with main functions including electrical inspection, phase calibration and phase sequence measurement. It uses double shielding and brand-new digital circuits, with strong anti-interference, accorded with EMC standards, suitable for various electromagnetic interference situations.

The high voltage phase signal of measured lead will be transmitted directly after treatment, the handset will receive and make phase comparison, determine the results after phase detection, real-time display phase angle difference and vector. It uses wireless transmission technology, safe and reliable, fast, and accurate, suitable for using at different voltage levels (10V-500KV). When checking the grid structure, it can accurately identify the relative phase of different leads for the three-phase connected line, without any electrical connection between two measurement components, which makes the application of the measurement device very flexible and safe.

Features

Voltage range: 10V~500KV, applicable for various voltage grades.
Accuracy: short distance: error ≤±3°; long distance: error ≤±3°.
Sampling rate: 10 times/second.
Date and time setting, date and time adjustment, easy for users to browse, view the historical data.
Backlight setting: normally on, normally off, user-defined within 0~999s.
Auto shut-down: never, user-defined within 0~999 minutes.
In-phase: ≤20° (user-defined if phase threshold is within 0-90°, default 20°)
Out-phase: >20° (user-defined if phase threshold is within 0-90°, default 20°)
On-site calibration function: on-site calibration can be carried out on the tested wire to ensure the accuracy of phase angle.
Multiple mode design, better applicability, more secure, more convenient.
Unique human-machine interface, simple operation.
FCC antenna design, stronger signal, easier to penetrate walls, doors, and barriers.
Double shielding, strong anti-interference, in full compliance with EMC standards.
Charts and data display, easier to read, with date and time display function.
Qualitative measurement: display by acousto-optic signal.
Quantitative measurement: real-time display of phase angle difference, error ≤5°.
Phase sequence check: positive phase sequence, negative phase sequence (120°, 240°).
Under GPS satellite timing service, the detection distance between detector Xa and Ya is ≥500km.
Data storage capacity of 2000 groups. It can query and access to historical data.
The length of standard insulation rod is 4m, and the applicable voltage grade of insulation rod is ≤ 220kV.

Technical Parameters

Voltage range

10V~500kV

Power supply

Hand-held unit: large capacity lithium battery

Xa & Ya detector: AA size alkaline battery (1.5V) 3pcs

Wireless transmission

Visual distance 150m

In-phase

≤20° (user-defined if phase threshold is within 0-90°)

Out-phase

>20° (user-defined if phase threshold is within 0-90°)

Display accuracy

Quantitative measurement ≤5°

Resolution of phase angle

Phase sequence measurement

Phase sequence is determined through clockwise 120°/ counterclockwise 240°

Satellite timing range

2~30 minutes

Display

Positive type LCD screen, clear in the sunlight.

Working temperature

-35~+50℃

Storage temperature

-40~+55℃

Relative humidity

≤95%RH, condensing

Hand-held unit

0.31 kg

Detector Xa

0.16 kg

Detector Ya

0.16 kg