HCB-14 Circuit Breaker Analyzer | 12-Channel High Voltage Switchgear Dynamic Characteristics Tester
• Equipped with a large, wide-temperature, direct-view backlit LCD display for displaying data and graphs; supports LCD contrast adjustment and features a power-off memory function.
• Captures complete mechanical characteristic test data and corresponding waveform graphs with a single switch operation.
• Supports selection and customization of opening and closing speeds, enabling arbitrary analysis and meeting the speed measurement requirements of various switch models.
• Supports measurement of inherent opening and closing times, as well as phase and interphase synchronicity for 12 circuit breakers.
• Captures time parameters for each circuit breaker during the close-open, open-close, and open-close-open operations, including first-open time, first-close time, second-close time, metal shorting time, and no-current time.
• Accurately measures closing bounce time, number of bounces, bounce process, and waveform for each circuit breaker, and simultaneously records opening rebound amplitude.
• Real-time acquisition of opening and closing speeds, maximum speeds, and generates time-travel characteristic curves. 8. Supports measurement of total travel, opening distance, over-travel, overshoot, and rebound amplitude.
• Enables dynamic monitoring of opening and closing coil currents and generates current waveform.
• Integrated with a DC 0-300V/20A digitally adjustable circuit breaker operating power supply, it automatically completes low-voltage operating tests and accurately measures operating voltages.
• Flexible support for various sensor types, including acceleration, linear, and rotational sensors.
• Supports test data storage, with a built-in real-time clock that accurately records test dates and times for easy archiving and traceability.
• Supports stable connection to a PC via USB for convenient data exchange.
• Built-in printer quickly outputs data and graphs for immediate recording and storage. Test results can be printed on a variety of printers, offering strong compatibility and flexibility.
|
Functions |
Parameters |
||
|
Time |
Range |
20000.0ms |
Min. Resolution 0.01ms |
|
Error |
200 ms |
0.01ms±0.1ms |
|
|
2000 ms |
0.1ms±0.1ms |
||
|
20000 ms |
1ms±0.1ms |
||
|
Velocity |
Range |
20.00m/s |
Min. Resolution 0.01m/s |
|
Error |
0~2m/s |
±0.1m/s±1digital |
|
|
≥2m/s |
±0.2m/s±1digital |
||
|
Travel |
Vacuum breaker |
50.0mm |
0.1mm, error 0.1±1digital |
|
SF6 circuit breaker |
300.0mm |
1mm, error 0.1±1digital |
|
|
Oil circuit breaker |
600.0mm |
1mm, error 0.1±1digital |
|
|
Current |
Max range |
20.00A |
resolution0.01A |
|
Output power |
DC0-300V digital adjustable / 20A (instantaneous working), resolution 1V. |
||
|
Insulation resistance |
> 2MΩ |
||
|
Dielectric strength |
Shell can withstand power frequency voltage 1.5kV at 1 minute without flash-over and arcing |
||
|
Temperature |
-10--40℃ |
||
|
Humidity |
≤80%RH |
||
|
Air Pressure |
86-106kpa |
||
|
Dimension |
360mm* 280mm* 300mm |
||
|
Weight |
10kg |
||