OEM Best earth tester megger Suppliers – GDHX-9500 Phase Detector – HV Hipot

OEM Best earth tester megger Suppliers – GDHX-9500 Phase Detector – HV Hipot

Brief Description:


Product Detail

Product Tags

Related Video

Feedback (2)

Our well-equipped facilities and great good quality regulate throughout all stages of manufacturing enables us to guarantee total buyer gratification for Measure Capacitor In Circuit, Capacitor Setting On Multimeter, Capacitance Voltage Meter, Together with our efforts, our products and solutions have won the trust of clients and been very salable each here and abroad.
OEM Best earth tester megger Suppliers – GDHX-9500 Phase Detector – HV Hipot Detail:

General Information

GDHX-9500 Phase Detector is mainly used in electric power lines, phase and phase sequence calibration in substation, with main functions including electrical inspection, phase calibration and phase sequence measurement. It uses double shielding and brand new digital circuits, with strong anti-interference, accorded with EMC standards, suitable for various electromagnetic interference situations.

The high voltage phase signal of measured lead will be transmitted directly after treatment, the handset will receive and make phase comparison, determine the results after phase detection, real-time display phase angle difference and vector.It uses wireless transmission technology, safe and reliable, fast and accurate, suitable for using at different voltage levels (6V-500KV). When checking the grid structure, it is able to accurately identify the relative phase of different leads for the three-phase connected line, without any electrical connection between two measurement components, which makes the application of the measurement device very flexible and safe.

Security Matters

● Using wireless transmission technology, its basic working principle is real-time phase comparison.

● Please observe and follow the regulation to use this product, in order to ensure the safe operation of the instrument, the ends of X and Y detector are not allowed to make withstand voltage test.

● The metal head parts of the insulating rod is strictly prohibited to contact with any objects during the test.

● Please comply with the national power industry safety regulations of preventive test for safety tools and products.

● Please pay attention to the training and examination for staffs who work on high-voltage live lines or near the high-voltage lines.

● Phase calibration on live equipment must be carried out by insulating rod.

Note: The safe usage length and test standards of insulating rod for “Wireless Phase Detector”.

(Excerpting from “Electrical safety working regulations of State Grid Corporation”.)

1. Safety distance between staff and the charged body during live operation.

Voltage Level

10kV

35kV

66kV

110kV

220kV

330kV

500kV

Safety Distance

0.4M

0.6M

0.7M

1.0M

1.8M

2.2M

3.4M

2. The minimum effective insulation length of insulating rod during live operation.

Voltage Level

10kV

35kV

66kV

110kV

220kV

330kV

500kV

Min. effective insulation length

0.7M

0.9M

1.0M

1.3M

2.1M

3.1M

4.0M

Note: The test standard of insulating tools checking test (subsection): applying power frequency 75kV each 300mm for 1min, if no breakdown, no flashover and over-heat, it is considered as qualify.

Features

● Test voltage: 10V-500kV, suitable for different voltage level.

● Accuracy: self-calibrating error ≤±3°.

● Sampling speed: 10 times/s.

● Date and time setting: date and time adjustment, easy for users to browse, view the historical data.

● Back-light time setting: normally on, normally off, 0-999s can be set by user.

● Auto power off setting: 0-999mins can be set by user.

● In-phase: ≤20° is considered as in-phase (phase threshold within 0-90°, can be set by user. The system default is 20°.)

● Out-phase qualitative: >20° (phase threshold within 0-90°, can be set by user. The system default is 20°.)

● Field calibration function: on-site calibration for measured lead, ensure the accuracy of phase angle.

● Transmission distance between handset and X, Y detector: X≤150m, Y≤150m.

● Multiple mode design, with strong applicability, safer and more convenient.

● Unique human-computer interaction interface, simple operation.

● FCC antenna design, the signal is stronger and easier to penetrate the blocking of wall, door, or barrier.

● Double shielding, strong an-ti interference, in full accordance with EMC standards.

● Charts and data display, more convenient and easier to read.

● Qualitative measurement, display by sound and light signal.

● Quantitative measurement, real-time display phase angle difference, error≤5°.

● Phase sequence calibration, positive phase sequence, negative phase sequence (120°, 240°).

Specifications

Test voltage

10V-500kV

Power supply

Handset: No.5 AA alkaline battery 2 sections (1.5V)

X and Y detector: No.7 AA alkaline battery 2 sections (1.5V)

Wireless transmission distance

Visual distance 150m

In-phase

Phase angle deviation≤20° (threshold within 0-90°, can be set by user self. )

Out-phase

Phase angle deviation>20° (threshold within 0-90°, can be set by user self. )

Display accuracy

Quantitative measurement≤3°

Phase angle resolution

1°

Phase sequence measurement

Through 120° clockwise/240°anti-clockwise to determine and indicate phase sequence

Display

Positive display LCD, clearly display under the sunshine

Operation temperature

-35℃-+50℃

Storage temperature

-40℃-+55℃

Relative humidity

≤95% RH, Non-condensate

Handset

0.31kg

X detector

0.13kg

Y detector

0.13kg


Product detail pictures:

OEM Best earth tester megger Suppliers –  GDHX-9500 Phase Detector – HV Hipot detail pictures

OEM Best earth tester megger Suppliers –  GDHX-9500 Phase Detector – HV Hipot detail pictures


Related Product Guide:

Our well-equipped facilities and exceptional good quality manage throughout all stages of production enables us to guarantee total shopper satisfaction for OEM Best earth tester megger Suppliers – GDHX-9500 Phase Detector – HV Hipot , The product will supply to all over the world, such as: Washington, Bangalore, US, We have constructed strong and long co-operation relationship with an enormous quantity of companies within this business in Kenya and overseas. Immediate and specialist after-sale service supplied by our consultant group has happy our buyers. Detailed Info and parameters from the merchandise will probably be sent to you for any thorough acknowledge. Free samples may be delivered and company check out to our corporation. n Kenya for negotiation is constantly welcome. Hope to get inquiries type you and construct a long-term co-operation partnership.
  • It is not easy to find such a professional and responsible provider in today's time. Hope that we can maintain long-term cooperation.
    5 Stars By Paula from Korea - 2017.01.28 19:59
    This is a very professional wholesaler, we always come to their company for procurement, good quality and cheap.
    5 Stars By Evelyn from Poland - 2018.09.08 17:09

    Send your message to us:

    Write your message here and send it to us

    Send your message to us:

    Write your message here and send it to us