General Information
GDSF-411CPD SF6 gas comprehensive analyzer is a portable device designed to measure SF6 gas dew point, purity and decomposition product. The core component with chilled mirror method is used to test dew point, European sensor with infrared method to test SF6 gas purity and electrochemical sensor from Membrapor to test SF6 gas decomposition product. Besides, we also adopt professional hardware chips and excellent software algorithms of STMicroelectronics.
Application

Features

Specification
SF6 Humidity
| Measurement method | Chilled mirror method (Stirling Refrigeration) |
| Measurement range | Dew point -100℃–+20℃(90s for single point measurement), error: better than ±0.2℃ |
| Repeat-ability | ± 0.1 ℃ |
| Resolution | 0.01℃ |
| Display unit | ℃, ppm, ℃ P20(converted value at 20℃) |
SF6 Purity
| Measurement method | Infrared Measurement Principle (NDIR series sensors) |
| Measuring range | 0 ~ 100% SF6, error: better than ± 0.3%F.S. |
| Response time | [90%] 60s |
| Repeatability | ± 0.3% |
| Resolution | 0.01% |
| Display unit | % |
SF6 Decomposition Products
| Measurement method |
Electrochemical Measurements Principle (Electrochemical series sensors from Membrapor) |
| Measurement range |
SO2: 0 ~ 200ppmv H2S: 0 ~ 200ppmv CO: 0 ~ 500ppmv HF: 0 ~ 50ppmv |
| Accuracy |
SO2: 10ppmv ±3% H2S: 10ppmv ±3% CO: 50ppmv ±4% HF: 10ppmv ±3% |
| Repeat-ability |
SO2: 10ppmv ±2% H2S: 10ppmv ±2% CO: 50ppmv ±2% HF: 10ppmv ±2% |
| Resolution | 0.01ppmv |
| Display unit | ppmv |
General Parameters
| Power supply | 220VAC±10%, 50Hz, AC/DC use, continuous working is more than 8 hours. |
| Use environment temperature | -20–+60℃ |
| Environment humidity | 90%RH |
| Measurement value influence | No effect of pressure and flow |
| Dimension | 570*420*280mm |
| Weight | Not more than 20kg. |
Accessories
|
Main Tester |
1 piece |
|
Adapter |
1 set |
|
Teflon pipe (include flow adjustment valve and fast connector) |
1 set |
|
Tail pipe |
1 set |
|
Spare parts |
1 set |
|
Charger |
1 piece |
|
User’s Guide |
1 piece |
|
Test Report |
1 piece |
Product detail pictures:
Related Product Guide:
As for competitive prices, we believe that you will be searching far and wide for anything that can beat us. We can state with absolute certainty that for such quality at such prices we are the lowest around for OEM Best Gas Purity Check Suppliers – GDSF-411CPD SF6 Gas Comprehensive Analyzer – HV Hipot , The product will supply to all over the world, such as: Lisbon, Jamaica, Colombia, We are sincerely looking forward to cooperate with customers all over the world. We believe we can satisfy you with our high-quality products and perfect service . We also warmly welcome customers to visit our company and purchase our products.