OEM Best Ir Gas Leak Detectors Exporters – GDSF-411CPD SF6 Gas Comprehensive Analyzer – HV Hipot
OEM Best Ir Gas Leak Detectors Exporters – GDSF-411CPD SF6 Gas Comprehensive Analyzer – HV Hipot Detail:
General Information
GDSF-411CPD SF6 gas comprehensive analyzer is a portable device designed to measure SF6 gas dew point, purity and decomposition product. The core component with chilled mirror method is used to test dew point, European sensor with infrared method to test SF6 gas purity and electrochemical sensor from Membrapor to test SF6 gas decomposition product. Besides, we also adopt professional hardware chips and excellent software algorithms of STMicroelectronics.
Application

Features

Specification
SF6 Humidity
| Measurement method | Chilled mirror method (Stirling Refrigeration) |
| Measurement range | Dew point -100℃–+20℃(90s for single point measurement), error: better than ±0.2℃ |
| Repeat-ability | ± 0.1 ℃ |
| Resolution | 0.01℃ |
| Display unit | ℃, ppm, ℃ P20(converted value at 20℃) |
SF6 Purity
| Measurement method | Infrared Measurement Principle (NDIR series sensors) |
| Measuring range | 0 ~ 100% SF6, error: better than ± 0.3%F.S. |
| Response time | [90%] 60s |
| Repeatability | ± 0.3% |
| Resolution | 0.01% |
| Display unit | % |
SF6 Decomposition Products
| Measurement method |
Electrochemical Measurements Principle (Electrochemical series sensors from Membrapor) |
| Measurement range |
SO2: 0 ~ 200ppmv H2S: 0 ~ 200ppmv CO: 0 ~ 500ppmv HF: 0 ~ 50ppmv |
| Accuracy |
SO2: 10ppmv ±3% H2S: 10ppmv ±3% CO: 50ppmv ±4% HF: 10ppmv ±3% |
| Repeat-ability |
SO2: 10ppmv ±2% H2S: 10ppmv ±2% CO: 50ppmv ±2% HF: 10ppmv ±2% |
| Resolution | 0.01ppmv |
| Display unit | ppmv |
General Parameters
| Power supply | 220VAC±10%, 50Hz, AC/DC use, continuous working is more than 8 hours. |
| Use environment temperature | -20–+60℃ |
| Environment humidity | 90%RH |
| Measurement value influence | No effect of pressure and flow |
| Dimension | 570*420*280mm |
| Weight | Not more than 20kg. |
Accessories
|
Main Tester |
1 piece |
|
Adapter |
1 set |
|
Teflon pipe (include flow adjustment valve and fast connector) |
1 set |
|
Tail pipe |
1 set |
|
Spare parts |
1 set |
|
Charger |
1 piece |
|
User’s Guide |
1 piece |
|
Test Report |
1 piece |
Product detail pictures:
Related Product Guide:
abide by the contract", conforms on the market requirement, joins from the market competition by its good quality likewise as provides more comprehensive and superb support for customers to let them become large winner. The pursue of the company, is definitely the clients' pleasure for OEM Best Ir Gas Leak Detectors Exporters – GDSF-411CPD SF6 Gas Comprehensive Analyzer – HV Hipot , The product will supply to all over the world, such as: Bandung, Portland, Russia, Ensuring high product quality by choosing the best suppliers, we have also implemented comprehensive quality control processes throughout our sourcing procedures. Meanwhile, our access to a large range of factories, coupled with our excellent management, also ensures that we can quickly fill your requirements at the best prices, regardless the order size.