OEM Best Leak Testing Machine Suppliers – GDWS-311RC SF6 Gas Dew Point Tester – HV Hipot
OEM Best Leak Testing Machine Suppliers – GDWS-311RC SF6 Gas Dew Point Tester – HV Hipot Detail:
General Information
GDWS-311RC is ideal instrument to test dew point of SF6 gas. The core component is DRYCAP series sensors produced by Finland Vaisala company. With professional hardware chips and excellent software algorithms of STMicroelectronics, we have produced a new generation of gas moisture test instrument.
Application
● Moisture monitoring of SF6 gas electrical equipment for electric power
● SF6 gas cylinder gas quality test
● High purity gas manufacturing
● Semiconductor industry dry gas supply
● Research and development use
● Clean room/dry house monitoring
● Metal heat treatment site and laboratory industrial gas humidity detection, such as air, CO2, N2, H2, O2, SF6, He, Ar and other inert gases.
Features
● Better than ±2℃ measurement accuracy.
● All gas path are polymer material design, ensures no water wall hanging phenomenon and guarantees the test speed.
● The oil-free stainless steel body regulating valve is used to ensure the accuracy of the measured value.
● Advanced software algorithms improve the test accuracy of sensors.
● Combined chassis configuration solution, users can easily combine related instruments and accessories. The overall package is carried, which makes the user have a more relaxed experience.
● Start up test, no need to preheat and oscillate.
● Temperature conversion and pressure data correction.
● Fuzzy computing technology.
● High-power lithium battery power, realize AC and DC dual power supply. No on-site AC power is required. Lithium battery power supply continues to work for more than 8 hours without the need of an external power supply.
● Anti-electromagnetic interference circuit design to ensure product reliability.
● Gas recycling function, environment-friendly.
● The test data is stable and can provide both standard dew point values and converted dew point values at 20℃.
● The best test flow area shows that the user can adjust the gas flow intuitively and quickly. Reduce test time.
● The air inlet is designed with a miniature self-sealing joint, and the air path to be tested will not leak when the air path is disconnected.
Specification
● Measurement method: Resistive and Capacitive measurement principle
● Measurement range: dew point -80℃–+20℃(support ppmv)
● Accuracy: ±2℃
(when the dew point temperature is below 0℃, the sensor output is the frost point)
● Response time: 63% [90%]
+20→-20℃ Td 5s[45s]
-20→-60℃ Td 10s[240s]
● Resolution: 0.01℃
● Repeat-ability: ± 0.5℃
● Display unit: ℃, ppm, ℃P20(converted value at 20℃)
● Gas flow: 400-600ml/min
● Flow display: 0-1000mL digital flow meter
● Sample gas pressure: ≤1MPa
● Power supply: 220VAC±10%, 50Hz, AC/DC use, continuous working is not less than 8 hours.
● Use environment temperature: -20–+60℃
● Environment humidity: 90%RH
● Measurement value influence: No affect of pressure and flow
● Dimension: 395*295*155mm
● Weight: about 2kg
Accessories
| Main unit | 1 piece |
| Adapter | 1 set |
| Teflon pipe(include flow adjustment valve and fast connector) | 1 set |
| Tail pipe | 1 set |
| Spare parts | 1 set |
| Charger | 1 piece |
| User’s Guide | 1 copy |
| Test Report | 1 copy |
Product detail pictures:
Related Product Guide:
We've got a specialist, effectiveness staff to supply high quality service for our shopper. We always follow the tenet of customer-oriented, details-focused for OEM Best Leak Testing Machine Suppliers – GDWS-311RC SF6 Gas Dew Point Tester – HV Hipot , The product will supply to all over the world, such as: Ethiopia, Bangladesh, Hungary, We sincerely hope to cooperate with customers all over the world, if you would like to have more information, please kindly contact us, we are looking forward to building up a great business relationship with you.