OEM Best Portable Sf6 Gas Analyser Factories – GDJD-3A SF6 gas Density Relay Calibrator – HV Hipot
OEM Best Portable Sf6 Gas Analyser Factories – GDJD-3A SF6 gas Density Relay Calibrator – HV Hipot Detail:
Product Description
GDJD-3A SF6 gas Density Relay Calibrator is automatic calibrator, which uses embedded microprocessor to proceed performance calibration for all kinds of SF6 gas density relay. It is also a portable device which can make standard conversion for SF6 gas pressure at any environmental temperature. This device is mainly used for SF6 gas products production, maintenance and monitoring in power system.
Features
● Automatically calibrate density relay and pressure gauge.
● Compact design, small size, and light weight, easy to carry.
● Color LCD screen, Windows menu.
● The power supply has UPS function, suitable for field operation.
● With mini-printer, to print test result directly.
● Good sealing property, do not waste SF6 gas during calibration.
● The two ends of connection pipe has fast check valve, easy operation and avoid water and air entering into the pipe. No need to dismantle most of density relay to calibrate directly.
● There is automatic voltage protector for sampling point. If sampling point clip misconnecting with 220V voltage, it will not destroy device.
Functions
Automatically measure pressure when SF6 gas density relay alarm or disalarm at any environmental temperature. It also can convert it to standard pressure at 20℃, to realize alarm performance calibration.
Automatically measure pressure when SF6 gas density relay interlock or relive interlock at any environmental temperature. It also can convert it to standard pressure at 20℃, to realize interlock performance calibration.
If there is pressure gauge or density meter of tested SF6 gas density relay, it can calibrate the accuracy of pressure gauge or density meter.
Convert the SF6 gas pressure into standard pressure at 20℃.
Convert the standard pressure at 20℃ into pressure at any temperature.
Set multiple measurement for one density relay. The measurement result is average value.
Specifications
Power supply: AC/DC use, built-in rechargeable battery, AC 220V±10%, 50Hz
Accuracy: Class 0.25
Display: 3.5inch true color LCD screen
Printer: Needle type microprinter
Measurement pressure range: 0-1.0Mpa
Calibration pressure range: standard pressure 0-0.9Mpa at 20℃
Temperature range: -50℃–100℃
Dimension: 258*240*88mm
Weight: about 2.5kg
Pressure resolution: 0.0001Mpa
Temperature resolution: 0.1℃
Storage capacity: 50-100pcs
Communication port: USB2.0
Product detail pictures:
Related Product Guide:
Our products and solutions are greatly recognized and trustworthy by customers and may fulfill constantly changing financial and social requires for OEM Best Portable Sf6 Gas Analyser Factories – GDJD-3A SF6 gas Density Relay Calibrator – HV Hipot , The product will supply to all over the world, such as: Las Vegas, Brisbane, Jersey, High output volume, top quality, timely delivery and your satisfaction are guaranteed. We welcome all inquiries and comments. If you are interested in any of our products or have an OEM order to fulfill, please feel free to contact us now. Working with us will save you money and time.
This is a very professional and honest Chinese supplier, from now on we fell in love with the Chinese manufacturing.





