OEM Best Primary Current Injection Test Factory – GDKC-15 Series Circuit Breaker Analyzer – HV Hipot
OEM Best Primary Current Injection Test Factory – GDKC-15 Series Circuit Breaker Analyzer – HV Hipot Detail:
General Information
High voltage circuit breaker is one of the most important control equipment in the power system. GDKC-15 Series is used to test the dynamic characteristics of high voltage circuit breaker. It is easy to operate, with high accuracy.
GDKC-15 Series
| GDKC-15A | GDKC-15B | GDKC-15C | GDKC-15D | GDKC-15E | GDKC-15F | GDKC-15G | GDKC-15H | |
| Metal contact | 12 | 12 | 12 | 12 | 12 | 12 | 12 | 12 |
| Closing resistance | 6 | 6 | 6 | 6 | 6 | 6 | 6 | |
| Graphite contact | 3 | 3 | 3 | 3 | 6 | |||
| Double-ended grounding | 3 | 3 | 3 | 6 | ||||
| Dynamic resistance(Pre-insertion resistor) | 1 | 1 | 3 | 3 | 3 | 3 | 6 | |
| Static resistance | 1 | 1 | 3 | 3 | 3 | 3 | 6 | |
| Ground resistance | 3 | 6 |
Features
● It is suitable for the mechanical test of all types of SF6 switches, GIS combination appliances, vacuum switches and oil switches.
● Strong anti-interference ability. It can be easily tested and accurately measured in 500KV substation.
● Accelerometer (optional), linear sensor, rotary sensor, easy to install and simple.
● All the data of the switch mechanical characteristic test and the corresponding waveform map are obtained after the switch is actuated once.
● Store the field test data and built-in real time clock, which is convenient for archiving and saving the test date and time.
● With 10.1inch LCD screen, display all data and map, with background light, LCD contrast adjustment and power off memory.
● Friendly menu operation, easy to use. With built-in printer to quickly print all data results.
● Equipped with data analysis management software, which can be operated online with PC, with WORD format file. The test results can be output to all kinds of printers printing test reports to make the field test computerized.
● Open and close velocity selection and user-defined function set according to needs, suitable for the velocity measurement of any type of switches.
Performance
● Time:
12 contacts inherent open (close) time
In phase synchronization
Phase-to-phase synchronization
● Reclosing:
C-O, O-C, C-O-C time,
First open time, first close time, second close time, close-open time, dead time, no current time.
● Bouncing:
Close bounce time, times, process and waveform of each contacts.
Opening rebound amplitude of each contact.
Velocity: velocity at contact just opening and just closing, maximum speed, time-travel characteristic curve.
Travel: total travel, open distance, over travel, overshoot trip, rebound amplitude.
Current: open/close current, current waveform diagram of the open/close coil.
Operating voltage: built-in DC0~300V/20A digital, adjustable power source of breaker, automatically complete LV action test of circuit breaker and measure action voltage value of circuit breaker.
Closing resistance: pre-cast time, pre-pitch waveform and resistance value of the closing resistor of 6contacts. (optional)
Graphite contact: the open, closing time and dynamic waveform of the Siemens graphite contact switch with 3 or 6-way contacts.(optional)
Double-ended grounding: under 3 or 6-way dual-port grounding, it can accurately measure the opening and closing time. (optional)
Static resistance: 1*100A contact resistance measurement.
Dynamic resistance (Pre-insertion resistor): 1*100A change waveform of dynamic resistance during circuit breaker action.
Specifications
● Usage Environment
Input Power: 220V±10%, 50Hz±10%, Air Pressure: 86-106kpa
Temperature: -10-40℃ Humidity: ≤80%RH
● Safety Performance
Insulation Resistance>2MΩ
Dielectric Strength: Shell can withstand power frequency voltage 1.5kV at 1 minute without flashover and arcing.
● The Basic Parameters
Time: Range 20000.0ms, resolution 0.01ms, error 0.5%
Closing resistance: range 10kΩ, min. resolution 1Ω, error 0.5% (optional)
Graphite contact: range 200ms, min. resolution 0.1ms, error 0.5% (optional)
Double-ends grounding: range 200ms, min. resolution 0.1ms, error 0.5% (optional)
Static resistance: range 1uΩ~10mΩ, min. resolution 0.01μΩ, error 0.5%
Dynamic resistance: range 10mΩ, min. resolution 1μΩ, error 0.5%
Test current: DC 50A、100A(3 phase measured at the same time)
Velocity: Range 20.00m/s resolution 0.01m/s error 0.5%
Travel:
|
Types |
Range |
Resolution |
Error |
|
Vacuum breaker |
50.0mm |
0.1mm |
0.5% |
|
SF6 circuit breaker |
300.0mm |
1mm |
|
|
Oil circuit breaker |
600.0mm |
Current: range 20.00A, resolution 0.01A
Output power: DC 0-300V digital adjustable/20A (instantaneous working), resolution 1V.
Dimensions: about 360mm (L)* 280mm (W)* 300mm (H)
Weight: about 10kg
Packing List
| Main unit with 10.1-inch tablet | 1 pc |
| Accessory case | 1 pc |
| Charger for tablet | 1 pc |
| American standard adapter | 2 pcs |
| Rotary speed sensor | 1 pc |
| Linear speed sensor 50mm | 1 pc |
| Speed signal connection cable (5-core shielded wire) | 1 pc |
| Opening and closing control cable (3-core sheathed cable) | 1 pc |
| External trigger detects cable (red/black, 2-core) | 1 pc |
| Ground cable | 1 pc |
| Contact test cable (4-core sheathed cable) | 1 pc |
| Contact test extended cable (5M, yellow, green and red each one-piece, black 3pcs) | 6 pcs |
| Short cable (0.5m black, 2m black) | 2 pcs |
| Power cord | 1 pc |
| Universal Joint and magnet base | 1 set |
| Special fixed installation accessories | 1 set |
| Test clips and thimbles | 18 pcs |
| Contact resistance test cable (5M) | 1 pc |
| Print paper | 2 rolls |
| USB cable | 1 pc |
| User’s guide | 1 pc |
| Factory test report | 1 pc |

Product detail pictures:
Related Product Guide:
We are ready to share our knowledge of marketing worldwide and recommend you suitable products at most aggressive costs. So Profi Tools offer you finest benefit of money and we are ready to produce alongside one another with OEM Best Primary Current Injection Test Factory – GDKC-15 Series Circuit Breaker Analyzer – HV Hipot , The product will supply to all over the world, such as: Mexico, Zimbabwe, Swaziland, Make sure you genuinely feel free to send us your requirements and we are going to respond for you asap. We now have got a skilled engineering group to serve for your just about every detailed needs. Cost-free samples could be sent to suit your needs personally to understand much more information. In an effort to meet your requires, be sure to seriously feel free to make contact with us. You may send us emails and contact us directly. Moreover, we welcome visits to our factory from around the globe for much better recognizing of our organization. nd objects. In our trade with merchants of numerous countries, we usually adhere for the principle of equality and mutual benefit. It is really our hope to market, by joint efforts, each trade and friendship to our mutual advantage. We look forward to getting your inquiries.