We offer wonderful energy in high-quality and improvement,merchandising,product sales and marketing and advertising and procedure for Higher Capacitance, Ultra High Voltage Pulse Generator, Capacitance Test Multimeter, Welcome any of your inquiries and concerns for our products, we look forward to establishing a long-term business relationship with you in the near future. contact us today.
OEM Best three phase relay test equipment Exporters – GDJB-6000M Smart Substation Relay Protection Test System – HV Hipot Detail:

GDJB-6000M Smart Substation Relay Protection Test System is a new generation of intelligent relay protection tester designed according to “Smart Substation Relay Protection Technical Specifications” and “Smart Substation Technical Guidelines”. It can not only realize the full function test of the optical digital protection device (IEC61850, smart digital station), but also carry out full function test on the traditional protection device (conventional station).

GDJB-6000M is a portable new product independently developed through the use of technologies such as embedded real-time operating systems, high-performance embedded processors, and large-scale logic devices, combined with power field conditions and numerous power user experiences. It is widely applicable to power plants, substations, equipment manufacturers, enterprises and institutions, as well as other research institutes that need to carry out relay protection testing or inspection.

GDJB-6000M adopts an engineering management scheme to manage the test; project management adopts a three-layer model of protection equipment, protection type, and test point to manage the test. The structure is very clear; It supports analog output, and can simultaneously carry out the output of the analog quantity and send & receive GOOSE messages; Provides multiple ways to configure SV and GOOSE messages, including manual settings, network detection, and importing SCL files; The optical digital message has a very flexible configuration of the transceiver, which can send multiple SV and GOOSE messages with 1 optical port, and the same SV and GOOSE messages can be sent through multiple optical ports.

Applicable Standards

DL/T 860 Series Standard “Substation Communication Network and System”
DL/T 624-2010 “Technical Conditions for Relay Protection Microcomputer Based Test Equipment”
GBT 7261-2008 “Basic Test Method for Relay Protection and Safety Automatic Devices”
IEC 60255-24:2001 “Electrical relays – Part 24: Common format for transient data exchange (COMTRADE) for power systems”

Features

● Smart Test Module
Intelligent test template editing is supported. Test items can be randomly added during the test process and saved as reusable test project files to improve the test efficiency in the final stage of inspection and elimination.Strong software functions. Real time display waveform, max. Peak and location. The software can check and analyze certain phase waveform. Windows can be zoomed in and out. One section data can be spectral analyzed and spectrum content of discharge waveform can be analyzed.

● Automatic testing
With on-site protection and digital protection automatic test function, all test items of a single protection device can be completed with one-key.The test data and transient discharge waveform can be saved automatically or manually.

● Digital/analog output
It can test the merging unit, protection, measurement and control devices, and intelligent terminals of digital substations, and can also test devices such as analog protection and transformer unit.

● Simultaneous output of analog and digital quantities
It supports simultaneous analog output and GOOSE message sending and receiving.

● Multiple scanning modes
Supports amplitude, phase, frequency, impedance, vector, sequence, and power are carried out by manual or automatic test, also supports automatic change test according to the method of gradation, slip and synthesis.

● Safety and alarm
With over-heating and over-current protection, the current source has an open-circuit protection and alarm function, and the voltage source has an overload and short-circuit protection function.

● Virtual terminal graphical display
Support virtual terminal graphical display function, the data flow is clear.

● Send and receive messages at the same time
Support IEC61850-9-1, IEC61850-9-2 and GOOSE optical digital message output. The GOOSE signal can be sent and received independently, and it can also send and receive by an optical Ethernet interface with IEC 61850-9-2.

● FT3/Extended FT3
Support FT3, extended FT3 and DL/T 282 message output, and support 2M/4M/6M/8M/10M baud rate UART encoding and 5M/10M/20M Manchester encoding.

● Abnormal test
With analog message abnormality function, it can simulate abnormality in quality, sending frequency jitter, delay anomaly, packet loss, out of step, serial number jump, maintenance mode, state virtual change and other tests.

● Fault playback
Supports fault simulation and COMTRADE format data playback function.

● MMS service
With MMS reading and writing function, can read and write intelligent IED equipment settings and other configuration information.

● Time synchronization and time giving
With synchronous trigger function, support for direct access to GPS/BD antenna for the time synchronization, also supports IRIG-B, PPS and PTP 1588 timing mode and can support external output IRIG-B, PPS and PTP 1588 time giving signal.

● Hard contact binary input and binary output
The input quantities is active and passive adaptive contacts, and the input type and input voltage are automatically recognized. The channels are isolated from each other, and the polarity reverse connection with alarm prompt.

● Message receiving and analysis
With the message receiving and analysis function, the received message can be opened with ZHNPA for analysis or export.

● Single fiber mode
The optical port supports single-fiber transmission and single-fiber reception and supports optical power testing.

● Analog small signal
It is equipped with analog small signal interface, support 12 way analog small signal input, can measure -7V~ 7V AC voltage, support 12 way analog small signal output, and can output -7V~ 7V AC voltage.
● Touch operation
Equipped with a 10.4 inch high-resolution display that supports touch operation.

● Wireless connection
Provide remote test function, with WiFi module, user-friendly.

Specifications

AC voltage source output Range: 6×120 V, 120V/60VA per way
Accuracy: ±10mV at 0.2~2V; ±0.2% at 2V~120V
Resolution: 1mV
AC current source output Range: 6×30A, 30A/150VA per way
Accuracy: ±10mA for 0~500mA; ±0.2% for 500mA~30A
Resolution:  1mA
Output phase Range:  0~360°
Accuracy: ±0.1°
Resolution:  0.1°
Output frequency Range:  0~1000Hz
Accuracy:<±0.001Hz (0~65Hz)
<±0.01Hz(65~450Hz)
<±0.02Hz (450~1000Hz)
Resolution:  0.001 Hz
DC voltage source output Range:  6 way, each way 0~130V/60VA
Accuracy: 0.2%
DC current source output Range:  6 way, each way 0~20A/100VA
Accuracy: 0.2%
IEC 61850 communication interface Number of ports: 6 pairs are 100M adaptive; 2 pairs are 100/1000M adaptive
Interface Type: LC
Wavelength: 1310nm
IEC 60044 communication interface Number of ports: 6 transmit ports, 2 receive ports
Interface Type: ST
Wavelength: 850nm
Synchronization interface Quantity: 1*GPS/BD ANT; 2*IRIG-B/PPS optical signal-1 for timing, 1 for time giving;  2 pairs* IRIG-B/PPS electrical signals-1 pair of timing, 1 pair of time giving; 1 pair* IEEE 1588;
Interface type: GPS/BD ANT, IRIG-B/PPS optical signal; IRIG-B/PPS electrical signal; IEEE 1588
Time measurement Range:10ms~9999.999s
Accuracy: 1ms
Switch input Quantity: 8 pairs
Interrupting Capacity: DC250V/0.5A
Switch output Quantity: 6 pairs, of which 2 pairs are for fast opening
Wireless connection Interface Type: WIFI
Wired connection (Ethernet communication interface) Number of ports:l 2
Interface type: 100 megabytes LAN port, RJ45
Power supply Voltage: AC/DC 220V, allowable deviation: -20%~15%
Frequency:  47~65 Hz
Analog small signal input Number of channels: 12 way;
Interface Type: Aviation Plug, AC Voltage
Analog small signal output Number of channels: 12 way;
Interface Type: Aviation Plug, AC Voltage
USB interface Quantity: 2
Working environment conditions Working temperature: -20°C~70°C
Humidity: ≤95%, no condensation
Others Weight: 15 kg
Size: 360×480×190(mm)
Online interface: RJ45
Display: 10.4 inch touch screen 1024*768 true color LCD display 

Product detail pictures:

OEM Best three phase relay test equipment Exporters –  GDJB-6000M Smart Substation Relay Protection Test System – HV Hipot detail pictures

OEM Best three phase relay test equipment Exporters –  GDJB-6000M Smart Substation Relay Protection Test System – HV Hipot detail pictures

OEM Best three phase relay test equipment Exporters –  GDJB-6000M Smart Substation Relay Protection Test System – HV Hipot detail pictures

OEM Best three phase relay test equipment Exporters –  GDJB-6000M Smart Substation Relay Protection Test System – HV Hipot detail pictures


Related Product Guide:

Our pursuit and corporation aim should be to "Always satisfy our consumer requirements". We carry on to build and style and design remarkable quality items for both our outdated and new clients and reach a win-win prospect for our clients at the same time as us for OEM Best three phase relay test equipment Exporters – GDJB-6000M Smart Substation Relay Protection Test System – HV Hipot , The product will supply to all over the world, such as: Guyana, US, Kuala Lumpur, We have a professional sales team, they have mastered the best technology and manufacturing processes, have years of experience in foreign trade sales, with customers able to communicate seamlessly and accurately understand the real needs of customers, providing customers with personalized service and unique products.
  • The factory workers have a good team spirit, so we received high quality products fast, in addition, the price is also appropriate, this is a very good and reliable Chinese manufacturers.
    5 Stars By Bruno Cabrera from Switzerland - 2018.08.12 12:27
    Product quality is good, quality assurance system is complete, every link can inquire and solve the problem timely!
    5 Stars By Renee from Vancouver - 2018.06.05 13:10

    Send your message to us:

    Write your message here and send it to us

    Send your message to us:

    Write your message here and send it to us