OEM Best Voltage Ac Supplier – VLF AC Hipot Test Set – HV Hipot
OEM Best Voltage Ac Supplier – VLF AC Hipot Test Set – HV Hipot Detail:
Withstand voltage test is an essential preventive test for electrical equipment. It is divided into two parts: AC and DC withstand voltage test. AC test can be further divided into power frequency, variable frequency and 0.1Hz very low frequency test, among which the last one is highly recommended by IEC, due to its remarkable advantages.
Following is a comparison for DC, Power Frequency, Variable Frequency, and 0.1Hz test.
Aspects |
DC |
Power Frequency |
Variable Frequency |
0.1Hz |
Equivalency |
poor |
good |
good |
good |
Insulation Damage |
strong |
slight |
slight |
slight |
Operation Safety |
relatively low |
relatively low |
relatively low |
high |
Wiring Difficulty |
complicated |
complicated |
most complicated |
simple |
Volume |
smallest |
largest |
large |
small |
In fact VLF test is the substitute for power frequency test. It is suitable for testing electrical equipment with large capacitance (like power cable, power capacitor, motor, and generator).
Description
The new generation of VLF series 0.1Hz VLF AC Hipot Test Set developed by HV Hipot adopts “Smart Quick” intelligent power test system (Soft No. 1010215, trademark registration number 14684781), HV HIPOT company introduced the latest international power electronic components and the latest ARM7 microcontroller technology, further reducing the size and weight of the equipment. The operation is easier, and the performance is more stable.
Features
● Advanced technology adopts digital frequency conversion technology, fully automatic microcomputer control, voltage boost, step-down, measurement, protection, etc.
● Control part and High-voltage part adopt an integrated structure design, and only a high voltage wire and ground wire are needed to connect to the tested product without the intermediate connection wire.
● Trolley-style design is convenient for transportation in various working environments, and its small size and light weight are very conducive to outdoor operations(80kV).
● Over-voltage protection and over-current protection. Action time is no longer than 10ms.
● The control unit and the booster are connected at low voltage, with photoelectric isolation control, safe and reliable to use.
● Closed-loop negative feedback circuit is adopted. No capacity rising during outputting.
● Capacitive touch screen, LCD graphic display, automatic storage, and printing.
● 0.1Hz, 0.05Hz and 0.02Hz can be chosen, which ensures a wide test range.
Specifications
● Peak voltage: 30kV
● Test frequency: 0.1Hz, 0.05Hz and 0.02 Hz (selectable)
● Maximum load capacity: 1.1μF@0.1Hz / 2.2μF@0.05Hz / 5.5μF@0.02Hz
● Measurement accuracy: 3%.
● Voltage peak value error: ≤3%.
● Voltage waveform distortion: ≤5%.
● Working environment: indoor or outdoor; -10℃-+40℃; 85%RH
● Fuse: 8A (30kV)
● Power supply: 220V ±10%, 50Hz ±5% (If using a portable generator, make sure the output voltage and frequency are stable. Power >3kW, frequency 50Hz, voltage 220V±5%.)
● Capacitance of the tested object shall not exceed the max. rated capacitance of the instrument.
Product detail pictures:
Related Product Guide:
We're going to dedicate ourselves to offering our esteemed shoppers with the most enthusiastically considerate solutions for OEM Best Voltage Ac Supplier – VLF AC Hipot Test Set – HV Hipot , The product will supply to all over the world, such as: Mumbai, Berlin, Miami, With the goal of "zero defect". To care for the environment, and social returns, care employee social responsibility as own duty. We welcome friends from all over the world to visit and guide us so that we can achieve the win-win goal together.
By Marina from Belize - 2018.05.22 12:13
We are old friends, the company's product quality has been always very good and this time the price is also very cheap.
By Lulu from Seattle - 2018.12.14 15:26