We have been also concentrating on enhancing the things management and QC method so that we could preserve terrific edge inside the fiercely-competitive enterprise for Surge Tester, Surface Partial Discharge, Tan Delta Kit, We have now confident that we can easily offer the premium quality products and solutions at resonable price, good after-sales services into the buyers. And we're going to produce a dazzling future.
China High Quality Partial Discharge Detector Is A Device That Measures Of Detects Exporters – GDJF-2008 Partial Discharge Analyzer – HV Hipot Detail:

GDJF-2008 Partial Discharge Detector is measuring partial discharge for the products such as transformers, mutual inductors, HV switches, zinc monoxide arresters and power cables. It also can make type tests and monitor insulation operation.
This type has the advantages of high sensitivity, wide range of capacitance, being well equipped for input unit impedance detecting and more variants of frequency bands (9 in all). After proper setting, the discharge impulse amount can be read directly. The indicating and digital meters are shown simultaneously.
This detector is widely applied in power stations, manufacturers, and institutions.

Use Condition

● Ambient temperature: 0-40℃±2℃.
● Relative humidity: ≤80%
● Power supply: 220V±10%, 50HZ.
● No violent vibration and mechanical shock.
● The device should be placed in the environment with no dust and corrosive, good ventilation. It should not be interfered by strong electromagnetic.
● Earthing requirements: earthing resistance <1Ω.
● Capacitance range to be tested 6PF-250μF.
● Testing sensitivity (shown in Table.1).

Input unit No.

Tuning capacitance

Unit

Sensitivity(pC) (Unsymmetrical circuit)

1

6-25-100

pF

0.02

2

25-100-400

pF

0.04

3

100-400-1500

pF

0.06

4

400-1500-6000

pF

0.1

5

1500-6000-25000

pF

0.2

6

0.006-0.025-0.1

mF

0.3

7

0.025-0.1-0.4

mF

0.5

8

0.1-0.4-1.5

mF

1

9

0.4-1.5-6.0

mF

1.5

10

1.5-6.0-25

mF

2.5

11

6.0-25-60

mF

5

12

25-60-250

mF

10

7R

Resistance

 

0.5

● Amplifier band
Low terminal: 10KHZ, 20 KHZ, 40 KHZ (optional)
High terminal: 80 KHZ, 200 KHZ, 300 KHZ (optional)

● Amplifier gain adjustment
Coarse control – there are 6 gears for coarse tuning, the gain of each gear is 20±1db
Fine control ≥ 20 db

● Time windows
Width of window, adjustable 15o—150o
Window position, adjustable 0o—170o
Two windows can be opened simultaneously or separately.

● Discharge meter
Digital display
PD display: LED 3½ digits
0-100.0 limit of error <±3% (full scale)

● Ellipse time base
Frequency: 50Hz and arbitrary frequency
Elliptic display color is yellow
Elliptic rotation: each gear is 30°, 180 ° rotation can be made.
Display: ellipse – straight line
High frequency time base elliptical input voltage less than 220 V, intake power < 1 VA

● Waveform lock
Lock required waveform of any time to facilitate observation and analysis

● Testing Voltage meter
Range: 100KV (Can be expanded)
Display 31/2 digital voltage meter
Accuracy: better than ±2% (full scale)

● Inside, outside the zero-mark function
● Dimensions: 450×450×190 mm
● Weight: about 16kg


Product detail pictures:

China High Quality Partial Discharge Detector Is A Device That Measures Of Detects Exporters –  GDJF-2008 Partial Discharge Analyzer – HV Hipot detail pictures

China High Quality Partial Discharge Detector Is A Device That Measures Of Detects Exporters –  GDJF-2008 Partial Discharge Analyzer – HV Hipot detail pictures


Related Product Guide:

The business keeps to the operation concept "scientific management, premium quality and efficiency primacy, customer supreme for China High Quality Partial Discharge Detector Is A Device That Measures Of Detects Exporters – GDJF-2008 Partial Discharge Analyzer – HV Hipot , The product will supply to all over the world, such as: Iraq, Sri Lanka, Costa Rica, Why we can do these? Because: A, We are honest and reliable. Our items have high quality, attractive price, sufficient supply capacity and perfect service. B, Our geographical position has a big advantage . C, Various types: Welcome your inquiry, It might be highly appreciated.
  • We have been cooperated with this company for many years, the company always ensure timely delivery ,good quality and correct number, we are good partners.
    5 Stars By Amy from Monaco - 2017.09.09 10:18
    In China, we have purchased many times, this time is the most successful and most satisfactory, a sincere and realiable Chinese manufacturer!
    5 Stars By Frances from Austria - 2017.11.01 17:04

    Send your message to us:

    Write your message here and send it to us

    Send your message to us:

    Write your message here and send it to us