GDHG-106B CT/PT Analyzer

GDHG-106B CT/PT Analyzer

Brief Description:

GDHG-106B is a multifunctional tool specially designed for analyzing current transformers and voltage transformers of protection or measurement use. The operator only needs to set values for test current and voltage, the instrument will automatically boost voltage and current, and then show test results in a short time. Test data can be saved, printed, and uploaded to PC through USB interface.


Product Detail

Product Tags

Features

● Finish all testing items by itself, no need to connect auxiliary equipment.
● Intelligent controller is adopted.
● Built-in printer, to print results easily.
● Large screen LCD, graphically display.
● Auto display excitation knee point value, 5% and 10% error curve.
● Save 3000 groups data and it is not lost after power down.
● With USB port. The data can be saved in USB disk and read by PC (WORD format file).
● Portable design, suitable for on-site test.
● Engineering plastic box with damping, strong and reliable.

Specifications

Main functions

CT (protection type, metering type) PT
Voltage current characteristic curve (excitation characteristic) Voltage current characteristic curve (excitation characteristic)
Auto calculate knee point value Auto calculate knee point value
Auto display 5% and 10% error curve Turns ratio measurement
Turns ratio measurement Polarity determination
Ratio error measurement Ratio error measurement
Phase measurement (angular difference) Phase measurement (angular difference)
Polarity determination AC withstand test
Primary current injection test Secondary winding resistance measurement
AC withstand test Secondary burden measurement
Secondary winding resistance measurement
Secondary burden measurement
Fast Test (Iron core demagnetization comprehensive test, complete excitation, ratio and polarity test at one time)

Main parameters 

Item Parameter
Power supply AC220V±10%, 50Hz
Output 0-2500Vrms, 5Arms (20A peak)
Output current 0-1000A
Accuracy of excitation ≤0.5%(0.2% of the reading+0.3% of the range)
Secondary winding resistance measurement Range 0.1-300Ω
Accuracy ≤1.0% (0.4% of the reading+0.6% of the range)
Secondary actual burden measurement Range 5-500VA
Accuracy ≤0.5% (0.2% of the reading+0.3% of the range) ±0.1VA
Angular error measurement Accuracy 4min
Resolution 0.1min
CT ratio measurement Range ≤25000A/5A (5000A/1A)  
Accuracy ≤0.5% (0.2% of the reading+0.3% of the range)
PT ratio measurement Range ≤500KV
Accuracy ≤0.5% (0.2% of the reading+0.3% of the range)
Operation environment Temperature: -10℃-40℃, Humidity: ≤90%, Altitude: ≤1000m
Dimension & Weight Dimension: 345mm × 445mm × 380mm   
Weight: about 30kg 