GDYD-10100A 100kV AC/DC Hipot Test Set | 100kVA Automatic PLC Dielectric Strength Tester
• 10inch integrated industrial computer, with programmable controller PLC automation control.
• HV voltage, HV current, LV voltage, LV current are collected isolate and synchronously, with high-precision sensor and high-performance collection chip.
• The human-machine interface uses wireless mouse, keyboard operation, intelligent work process, automatic mode and manual mode for option.
• HV voltage, HV current, LV voltage, LV current, time, withstanding results and the HV curve dynamic can be displayed, clear and obvious.
• With over-voltage, over-current protection, and flashing protection. Set the output voltage, HV current upper limit, time and LV current protection (hardware has been set).
• Support stage boosting (5 stages), and the voltage value of each stage can be arbitrarily set to facilitate the detection of test object problems.•
• Zero-starting function. Test can be proceeded after the voltage is back to zero.
• Can store up to 8000pcs data in 3months.It has USB port to export data to USB disk.
• When setting voltage is arrived, it will be timing automatically. After timing, voltage will be back to zero.
• When the LV current is over setting value, the voltage will be cut off automatically and it will be back to zero. When the HV current is over setting value, the test object will be cut off by HV close/open device (automatic HV meter is optional for monitoring and tripping). When test continues and the flash-over setting value is exceeded, the voltage will be cut off automatically and back to zero.
• Anti-interference design, adapting to the harsh electromagnetic environment.
• Automatic error diagnosis, easy to discover and solve problems, with simple and convenient maintenance.
Manual system:
• Low voltage measurement range: 0-400V Resolution: 1V
• Low voltage current measurement range: 0.2-250A Resolution: 1A
• High voltage measurement range: AC 0~100KV, Resolution: 0.1kV
•HV ammeter measurement range: AC 0~1A , Resolution: 0.01A
• Timing range: 1S~99H
• Voltage accuracy ≤±1.5% (10%~100% range)
• Current accuracy ≤±1.5% (10%~100% range)
Automatic system:
• Low voltage measurement range: 0-400V Resolution: 0.01V
• Low voltage current measurement range: 0.2-250A Resolution: 0.01A
• High voltage measurement range: AC 0~100KV, Resolution: 0.01kV
l High voltage current measurement range: AC20~1000mA Resolution: 1mA
l Timing range: 0~999s
l Voltage accuracy ≤±1.5% (10%~100% range)
l Current accuracy ≤±1.5% (10%~100% range)