General Information
Test Object:
22.9kV Single Phase transformers and special transformers, load voltage and current: AC 0-650V/78A, AC 0-1200V/29A, AC 0-2400V/14.6A
The impedance of tested transformer is within 7%, HV side is 23kV, 11kV, 6kV. LV side is 0.05kV-2.4kV.
This test bench can conduct below test:
1. No-load test including no-load loss, the percent of no-load current to rated current.
2. Load test including load loss, impedance voltage percentage, automatic temperature conversion and load loss test under 30% or above full current.
3. Induced voltage test.
Features
● Manual record test data and save in the database.
● The data of No-load test can be corrected by waveform and rated voltage automatically.
● The data of Load test can be corrected by temperature (75℃, 100℃, 120℃, 145℃) and rated current.
● In No-load test, LV side voltage can be monitored.
● In Load test, HV side current can be monitored.
● All test functions and test process can be selected and controlled by buttons of front panel.
● All test results are corrected according to the requirement of GB1094, IEC60076 or ANSI C57.
● Test procedure can be proceed by PC software.
● All data can be stored and printed.
● With zero protection, over-current protection and over-voltage protection functions.
● CT/PT range switch automatically.
● The test bench will fully control to the whole loop circuit and monitor the measurement.
● Safety alarm system.
Specifications
Transformer Load and No-load Tester (Just for reference, the final model is Fluke Norma 4000)
Voltage range: 0-1000V
Current range: 0.25-20A, accuracy 0.2%.
Power accuracy 0.3%.
Power factor 0.050-1.000, accuracy 0.3%
Frequency 40-70Hz, accuracy 0.1%.
Power P
No-load current Io, %
No-load loss Po
Load loass Pk
Impedance voltage Uk
Power Po
Average line voltage Un
Average current In.
HV CT specifications
Voltage range: 3kV
Measuring range: 0.25A-110A
Accuracy 0.05%
Turns ratio is 100,50,30,20,10,5,2.5/1A
PT specifications
Voltage range: 0.1kV-3kV(50Hz-400Hz)
Accuracy 0.05%
Turns ratio is 3,2,1,0.5kV/0.1kV
Variable Frequency Power Supply
Input voltage: Single phase AC380V, 60Hz
Measuring range: 0-800V
Rated capacity: 30kVA
Output current: 0-37.5A
Output frequency: 180Hz, 240Hz, 400Hz±2%
Intermediate Transformer
Capacity: 40kVA
Input Voltage: Single phase 500V
Output Voltage: 0-650V-1200V-2400V
100kVA Single Phase Regulator
Input voltage: Single phase 380V/60Hz, output voltage 20-650V.
Max. Load current: 154A
It is non contact regulating, easy to use.
When input voltage is constant, it can adjust output voltage smoothly with load. It is designed by rated frequency 60Hz.
Design Requirement
All required test are equipped in the same bench, each function is independent. All test are automatic.
Transformer Characteristic Test(No-load and Load Test)
It is controlled by PC and supplied induced voltage regulator 100kVA, intermediate transformer 40kVA.
We can customize different rating models based on actual requirement.
Company Information
Product detail pictures:
Related Product Guide:
The pretty loaded projects management experiences and one to a person support model make the high importance of business enterprise communication and our easy understanding of your expectations for OEM Best Simulate Lightning Impulse Manufacturers – GDBT-1000kVA Transformer Test Bench – HV Hipot , The product will supply to all over the world, such as: Seattle, Georgia, San Diego, We've established long-term, stable and good business relationships with many manufacturers and wholesalers around the world. Currently, we've been looking forward to even greater cooperation with overseas customers based on mutual benefits. You should feel free to contact us for more details.
By Beulah from Sweden - 2018.07.27 12:26
Wide range, good quality, reasonable prices and good service, advanced equipment, excellent talents and continuously strengthened technology forces,a nice business partner.
By Rachel from New Orleans - 2018.06.09 12:42