GDQH-601-200 SF6 Gas Recovery Unit, SF6 Gas Recovery and Filling Device for HV Switchgear

GDQH-601-200 SF6 Gas Recovery Unit, SF6 Gas Recovery and Filling Device for HV Switchgear

Brief Description:

GDQH-601-200 SF6 gas recovery unit is manufactured according to the DL/T662-1999 standard “Sulfur Hexafluoride Charging and Recovery Device”. It consists of an SF6 compressor, vacuum pump, vacuum system with anti-oil-back device, condensation system, liquid storage tank, purification system with built-in regenerable dryer filter, dust filter, ball valve, vacuum gauge, and auxiliary facilities such as electrical control, pressure detection, thermometer and alarm devices, and control and instrument panel.

 Suitable for manufacturers of SF6 electrical appliances, GIS combined electrical appliances, and SF6 gas-insulated electrical equipment, as well as for users, operating and research departments.


Product Detail

Product Tags

Features

 

 • Vacuuming and vacuum measurement of the unit itself, SF6 switch, and GIS;

 • Vacuuming and vacuum measurement of the liquefaction tank;

 • Vacuuming and vacuum measurement of the unit itself;

 • Recharging the SF6 switch;

 •  Recovering SF6 gas from electrical equipment, including moisture and oil treatment;

 •Drying and purifying the recovered and recharged SF6 gas;

 • Recovering, liquefying, storing, and measuring the residual pressure of SF6 gas in SF6 electrical equipment;

 •200KG storage tank is located within the unit.

 • Compressing and storing SF6 gas.

 • This device is mobile.

Specifications

 

Type Refrigerant liquefaction, air cooling, hand-push mobile
Working temperature -10℃~40℃
recovering  Initial recovery pressure (Mpa) 0.8
Terminal pressure(Mpa) ≤0.05
Time required for 1m³ volume (h/m3) ≤1
Filling Initial recovery pressure (Mpa) ≤133
Terminal pressure(Mpa) 0.8
Time required for 1m³ volume (h/m3) ≤0.3
The time required to evacuate from 0.1 MPa to 133 Pa is (hours/m3). ≤0.45
Limiting Vacuum (Pa) ≤10
Annual leakage rate ≤1%
Purity of SF6 gas after recovery Water content(PPM/V) ≤60
Oil content(PPM/W) ≤5
Dust (um) ≤1
storage vessel Storage way Gaseous and liquid state
Pressure (MPa) 2.5
Volume (L) 200
Liquid storage volume (kg) 200
Liquefaction method Freezing liquefaction
Drying filter regeneration method Power supply Vacuum activation regeneration
Total power (kW) Three-phase 3Φ 415V with neutral wire
Noise dB(A) 9
Overall dimensions (mm) ≤75
Equipment weight (kg) 1500mm×1100mm×1600mm
Liquefaction method ≤680KG