GDYD-P-250/50 250kVA/50kV AC/DC Hipot Test Set | PLC Automatic Withstand Voltage Tester

GDYD-P-250/50 250kVA/50kV AC/DC Hipot Test Set | PLC Automatic Withstand Voltage Tester

Brief Description:

GDYD-P AC Hipot Test Set uses PLC controller, 2.4G ISM networking technology, and advanced human-machine interface, which make the operation easier. It can be used to the insulation strength test of various electrical products, electrical components, insulation materials under specified voltage to evaluate the insulation levels, and check the insulation defect of the subject, and judge the ability of overvoltage. It is widely used in electrical manufacturing departments, electrical operation departments, scientific research units and colleges.


Product Detail

Product Tags

Features

 

Automatic mode:

• 19inch integrated industrial computer, with programmable controller PLC automation control.

•HV voltage, HV current, LV voltage, LV current are collected isolate and synchronously, with high-precision sensor and high-performance collection chip.

•The human-machine interface uses wireless mouse, keyboard operation, intelligent work process, automatic mode and manual mode for option.

• HV voltage, HV current, LV voltage, LV current, time, withstanding results and the HV curve dynamic can be displayed, clear and obvious.

•With over-voltage, over-current protection, and flashing protection. Set the output voltage, HV current upper limit, time and LV current protection (hardware has been set).

• Supports intelligent control of the boost speed, and the voltage can be adjusted at speeds of 0.1kV/s, 0.2kV/s, 0.5kV/s, 1.0kV/s, 2.0kV/s, and 3.0kV/s, allowing users to choose freely.

• Zero-starting function. Test can be proceeded after the voltage is back to zero.

• Local storage. It has USB port to export data to USB disk.

• When setting voltage is arrived, it will be timing automatically. After timing, voltage will be back to zero.

•When the LV current is over setting value, the voltage will be cut off automatically and it will be back to zero. When the HV current is over setting value, the test object will be cut off by HV close/open device (automatic HV meter is optional for monitoring and tripping). When test continues and the flash-over setting value is exceeded, the voltage will be cut off automatically and back to zero.

• Anti-interference design, adapting to the harsh electromagnetic environment.

• Automatic error diagnosis, easy to discover and solve problems, with simple and convenient maintenance.

• Monitoring functions: High voltage, low voltage, high voltage current, zero position indicator, power indicator, operating indicator, timing indicator.

 

Manual mode

• Protection functions: Over-current protection, zero-position start protection, sound and light alarm reminder.

•Adopt new time relay, wider timing range (1S~99H).

• Adopt new current relay, more accurate and reliable, ensuring personal and equipment safety.

• Support manual control of the boost speed, which can be adjusted via the speed control knob on the panel.

• Manual/automatic mode is two independent operating systems, which are backup for each other; they can be operated independently in any mode, and each control system will not be affected by each other when a failure occurs.

Specifications

Manual system:

• Low voltage measurement range: 0-500V Resolution: 1V

• Low voltage current measurement range: 0.2-1000A Resolution: 1A

• High voltage measurement range: AC/DC 0~50kV Resolution: 0.01kV

• HV ammeter measurement range: 0~5A Resolution: 0.01mA

• Timing range: 1S~99H

• Voltage accuracy ≤±3% (10%~100% range)•

• Current accuracy ≤±3% (10%~100% range)

 

Automatic system:

• Low voltage measurement range: 0-450V Resolution: 0.1V

• Low voltage current measurement range: 0.2-1000A Resolution: 0.1A

• High voltage measurement range: AC/DC 0~50kV Resolution: 0.01kV

• High voltage current measurement range: AC20~5000mA Resolution: 0.01mA

• Timing range: 0~999s

• Voltage accuracy ≤±3% (10%~100% range)

• Current accuracy ≤±3% (10%~100% range)

• Dimension & weight: 1200*1030*1250mm 102KG

 

 Voltage regulator

• Input voltage: AC400V±10% 50Hz±1

• Output capacity: 250kVA

•  Low voltage output: AC 0~430V

•  Output current: 581A (Max)

• Dimension & weight: 1340*1000*2010mm  824KG

 

Oil Immersed Testing Transformer

•  Output capacity: 250kVA

• Low voltage (input) voltage: AC 0~400V

•  Low voltage (input) current: AC 0~625A

•  High voltage (output) voltage: AC/DC 0~50kV

• High voltage (output) current: 0-5000mA

• Measurement ratio: 500:1 Error: ±1%

• Impedance voltage: ≤9%;

•  No-load current: ≤1.1%;

•  Operation time: 5min on, 10min off intermittent cycle working system at rated capacity, long-term operation at 1/3 rated voltage and 1/3 rated current

•  Dimensions & weight: Φ1000*1180mm  650KG

 

HV Diode

• Rated frequency: 50Hz

•  Rated voltage: 70kV

•  Rated current: 0.2A

 

GDFR-C1-50 Voltage Divider 

GDFR-C1-50 is a universal HV measuring instrument that can be used in power systems, electrical appliances, and electronic equipment manufacturing departments to measure AC/DC high voltage.

•  Capacitance: 500pF

•  Voltage: 50kV

• Impedance: 640MΩ

•  Accuracy: AC1.5%, dc 1.0%

•  Frequency: Power frequency 50Hz

• Voltage ratio: 1000:1

• Dimensions & weight: Φ395*1170mm  12KG

• Use environment: Indoor use or outdoor use in sunny weather.